Power Supply Calculations

190

MS-9200UDLS PN 52750:E1 01/27/09

7.4 Calculating the Battery Size

Use Table 7.4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load
determines the battery size (in AH), required to support the control panel under the loss of AC
power. Complete Table 7.4 as follows:

1. Enter the totals from Table 7.3 on page 189, Calculation Columns 2 and 3 where shown

2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below)

3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere

hours

4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH)

5. Write the ampere hour requirements on the Protected Premises label located inside the

cabinet door

7.4.1 NFPA Battery Requirements

NFPA 72 Local, Proprietary, Central, Auxiliary and Remote Fire Alarm Systems require 24
hours of standby power followed by 5 minutes in alarm

7.4.2 Selecting and Locating Batteries

Select batteries that meet or exceed the total ampere hours calculated in Table 7.4 . The control
panel can charge batteries in the 7 AH to 18 AH range. The control panel cabinet is capable of
housing batteries up to 18 AH. Batteries larger than 18 AH require a UL listed external battery
charger and cabinet such as the BB-26, BB-55F or other UL listed external battery cabinet.

Table 7.4 Total Secondary Power Requirements at 24 VDC

Secondary Standby Load
(total from Table 7.3 Calculation
Column 3)
[ ]

Required Standby Time
(24 hours)

X[ ]

= AH

Primary Alarm Load
(total from Table 7.3 Calculation
Column 2)

[ ]

Required Alarm Time
(for 5 min., enter 0.084,
for 10 min., enter 0.168)

X[ ]

= AH

Sum of Standby and Alarm Ampere Hours

= AH

Multiply by the Derating Factor

X 1.2

Battery Size, Total Ampere Hours Required

= AH