B. mantel and wall projections – Heat & Glo Fireplace COSMO-I30 User Manual

Page 18

Advertising
background image

Heat & Glo • Cosmo-I30, Cosmo-I35 • 2239-900 Rev. H • 1/11

18

B. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specifi ed. Framing or fi nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).

Clearance to combustible material under the insert is 1/4
inch (6 mm). Clearance from top of fi replace opening for
combustibles extending 12 inches max. is 12 inches.

• Use leveling legs to raise insert minimum 1/4 inch (6 mm)

above combustible material or outer wrap of factory built
fi rebox.

Combustible facings must not extend behind the insert
surround. For non-combustible material specifi cations
refer to section 1.E.

Figure 5.3 Mantel Clearances

12 IN. MIN.

12 IN. MAX.

EXISTING NON-COMBUSTIBLE FACING

Figure 5.2 Fireplace Opening - Deep Surround

C

D

SURROUND

APPLIANCE

1-1/2 IN.

B

D

A

D

APPLIANCE

SURROUND

MINIMUM FIREPLACE SIZE

Location

COSMO-I35

COSMO-I30

Inches

Millimeters

Inches

Millimeters

A

D

Alternate Unit Width

33-3/16

843

29-1/16

738

B

D

Alternate Unit Depth

15-1/16

383

13-7/8

352

C

D

Alternate Unit Height

22-9/16

573

19-1/16

484

* Note: If exhaust collar on insert and fi replace damper do not line up, add 4 inches (102 mm) to minimum

fi replace height for bends in vent pipe.

TOP VIEW

SIDE VIEW