Hot gas reverse cycle kits (cont.) – Heatcraft Refrigeration Products Air Defrost RLC User Manual

Page 14

Advertising
background image

14

In the refrigeration cycle, the thermostatic expansion

valve bypass assembly check valve only allows refrigerant

flow through the thermostatic expansion valve and into

the evaporator coil. As the refrigerant vapor exits the coil

at the suction line, the check valve of the drain pan loop

check valve assembly prevents the refrigerant vapor flow

through the drain pan loop.
Factory engineered assemblies (kits) are available for both

shipped-loose and factory-installed at an additional cost

to complete the reverse cycle piping and components.

The suction line check valve assembly includes the

suction line check valve and the piping for both the

suction line and the connection to the drain pan loop

inlet header. In order for the suction line check valve

assembly to be mounted, the drain pan loop check

valve assembly must be used. The drain pan loop check

valve assembly includes the check valve, suction line

tee and a bent pipe. The thermostatic expansion valve

bypass assembly option includes the check valve, tee

and necessary piping. In order for the thermostatic

expansion valve bypass assembly option to be complete,

a thermostatic expansion valve must be selected by the

sales engineer. The thermostatic expansion valve bypass

assembly option is dependent on the body style of the

thermostatic expansion valves which includes the Sporlan

SQE, SBF, EG and the Alco HFESC body styles. The factory-

installed thermostatic expansion valve bypass assembly

option must have the thermostatic expansion valve selection included on the order for the hot gas unit cooler.
To increase the efficiency, higher performance and greater system protection, a heat exchanger may be

beneficial to the system. In order to use a heat exchanger, the thermostatic expansion valve bypass assembly

option must be modified. See the piping view in Figure 2. The modification includes rerouting the pipe from the

thermostatic expansion valve bypass check valve to the inlet connection of the liquid line to the heat exchanger.

A pipe needs to be routed from the liquid line outlet connection of the heat exchanger to the inlet connection of

the thermostatic expansion valve.
The electrical control option includes an adjustable defrost termination and fan delay control (DTFD) which is

standard. For an additional cost, an optional (2) control electrical system is available with one adjustable control

for defrost termination (DT) and one fixed control for the fan delay (FD). For both the DTFD and DT adjustable

controls, the remote bulb position is with the bulb strapped to the piping of the thermostatic expansion valve

bypass assembly option between the distributor sideport and the check valve. When the thermostatic expansion

valve bypass assembly is shipped-loose, the installer will need to position the remote bulb. When the thermostatic

expansion valve bypass assembly is factory-installed, the remote bulb should already be properly installed.

Hot Gas Reverse Cycle Kits (cont.)