Performance Data

Model GLC

Hot Gas Defrost | 60 Hz

Model

Capacity

Fan Data

10°F TD

-20°F SST

6°C TD

-29°C SST

No.

CFM

m

3

H

BTUH

Watts

6 F

ins P

er I

nch

GLC035

3,500

1,025

1

700

1,189

GLC040

4,000

1,170

1

700

1,189

GLC047

4,700

1,380

1

650

1,104

GLC065

6,500

1,900

2

1,400

2,379

GLC075

7,500

2,200

2

1,300

2,209

GLC090

9,000

2,640

2

1,300

2,209

GLC120

12,000

3,520

3

2,100

3,568

GLC140

14,000

4,100

3

1,950

3,313

GLC160

16,000

4,690

4

2,600

4,418

GLC180

18,000

5,280

4

2,600

4,418

GLC200

20,000

5,860

5

3,250

5,522

GLC240

24,000

7,030

6

3,900

6,627

GLC280

28,000

8,200

6

3,900

6,627

4 F

ins P

er I

nch

GLC041

4,100

1,200

1

690

1,172

GLC068

6,800

2,000

2

1,380

2,345

GLC080

8,000

2,340

2

1,380

2,345

GLC102

10,200

2,990

3

2,170

3,687

GLC136

13,600

3,990

4

2,760

4,690

GLC170

17,000

4,980

5

3,450

5,862

GLC204

20,400

5,980

6

4,140

7,035

GLC235

23,500

6,880

6

4,140

7,035

Model GLC

Hot Gas Defrost | 50 Hz

Model

Capacity

Fan Data

10°F TD

-20°F SST

6°C TD

-29°C SST

No.

CFM

m

3

H

BTUH

Watts

6 F

ins P

er I

nch

GLC035

3,325

974

1

630

1,070

GLC040

3,800

1,113

1

630

1,070

GLC047

4,465

1,308

1

586

995

GLC065

6,175

1,809

2

1,260

2,142

GLC075

7,125

2,087

2

1,170

1,989

GLC090

8,550

2,504

2

1,170

1,989

GLC120

11,400

3,339

3

1,891

3,213

GLC140

1,950

3,313

3

1,756

2,984

GLC160

2,600

4,418

4

2,341

3,978

GLC180

2,600

4,418

4

2,341

3,978

GLC200

3,250

5,522

5

2,927

4,973

GLC240

3,900

6,627

6

3,512

5,967

GLC280

3,900

6,627

6

3,512

5,967

4 F

ins P

er I

nch

GLC041

690

1,172

1

621

1,056

GLC068

1,380

2,345

2

1,243

2,111

GLC080

1,380

2,345

2

1,243

2,111

GLC102

2,170

3,687

3

1,954

3,320

GLC136

2,760

4,690

4

2,485

4,223

GLC170

3,450

5,862

5

3,107

5,279

GLC204

4,140

7,035

6

3,728

6,334

GLC235

4,140

7,035

6

3,728

6,334

For EC motors, use 60 Hz capacity and airflow values (Units with EC motors

operating at 50 Hz will not see a reduction in performance due to the electronic

control of the motor)

NOTE: When using the hot gas units with a hot gas

loop drain pan on 0°F applications and below, an

insulated drain pan is required.

Capacity Correction Factors For

Electric and Hot Gas Defrost Units

Saturated Suction

Temperature °F

+20

-10

-20

-30

Saturated Suction

Temperature °C

-7

-23

-29

-34

Multiply Capacity

By

1.15 1.04 1.00 0.90

Advertising
This manual is related to the following products: