Coil perfromance- chilled water mbh/sq ft – Heatcraft Refrigeration Products HCS User Manual

Page 22

Advertising
background image

22

* Note: correction factor = (enthalpy of air temperature - enthalpy of water temperature) in BTU /LB divided by 13.97.

Capacity Correction Factors* To Coil Performance

Of 67°F. Wb Air And 45 Entering Water

Ent Air WB

Entering Water Temperature °F.

TEMP. °F.

40

41

42

43

44

45

46

47

48

49

50

60

0.805

0.782

0.736

0.702

0.666

0.630

0.594

0.556

0.518

0.480

0.440

61

0.853

0.819

0.785

0.750

0.715

0.680

0.643

0.606

0.568

0.529

0.490

62

0.903

0.869

0.836

0.801

0.765

0.730

0.693

0.656

0.618

0.579

0.540

63

0.954

0.921

0.887

0.852

0.817

0.781

0.745

0.707

0.670

0.631

0.591

64

1.007

0.974

0.940

0.905

0.870

0.834

0.798

0.760

0.722

0.684

0.644

65

1.062

1.028

0.994

0.959

0.924

0.888

0.852

0.815

0.777

0.738

0.699

66

1.117

1.083

1.049

1.014

0.979

0.943

0.907

0.870

0.832

0.793

0.754

67

1.173

1.140

1.106

1.071

1.036

1.000

0.963

0.926

0.888

0.850

0.810

68

1.230

1.197

1.163

1.128

1.093

1.057

1.021

0.984

0.946

0.907

0.868

69

1.290

1.256

1.223

1.188

1.152

1.117

1.080

1.043

1.005

0.966

0.927

70

1.350

1.316

1.283

1.248

1.213

1.177

1.140

1.103

1.065

1.026

0.987

71

1.412

1.378

1.344

1.309

1.274

1.238

1.202

1.165

1.127

1.088

1.049

72

1.475

1.441

1.407

1.372

1.337

1.301

1.265

1.228

1.190

1.151

1.112

73

1.540

1.506

1.472

1.437

1.402

1.366

1.330

1.293

1.255

1.216

1.177

74

1.606

1.572

1.538

1.503

1.468

1.432

1.396

1.359

1.321

1.282

1.243

Coil Perfromance- Chilled Water MBH/SQ FT

1/2" and 5/8" tube, entering air 80°F. DB, 67°F. WB

Type A and Type 5, chilled water at 45°F., cooling capacities

MBH per SQ FT of coil face area (Max. water veocity= 3 fps)

Note: Please contact your representative for ARI ratings for coils. These tables are only estimates.

For estimates for other wet bulb and water temperatures, multiply by correction factor in

Table 20.

Actual capacity will vary

with coil circuiting

and flow rate

Table 19
Chilled

Water

FPM, Type A Coils (1/2" DIA.) FPM, Type 5 Coils (5/8" DIA.)

Rows

FPI

400

450

500

550

600

400

450

500

550

600

6

7.3

7.9

8.3

8.8

9.2

10.3

11.2

12.0

12.4

12.9

8

8.7

9.3

9.9

10.5

11.0

11.5

12.5

13.5

14.0

14.5

3

10

9.8

10.6

11.3

12.0

12.6

12.5

13.7

14.7

15.2

15.8

12

10.9

11.7

12.5

13.2

14.0

13.3

14.5

15.6

16.2

16.8

14

11.7

12.7

13.6

14.4

15.2

13.9

15.2

16.4

17.0

17.6

6

9.1

9.8

10.4

11.0

11.6

12.3

13.4

13.7

14.8

15.7

8

10.6

11.4

12.2

12.9

13.6

13.6

14.9

15.3

16.4

17.5

4

10

11.8

12.8

13.7

14.6

15.4

15.4

16.1

17.5

18.7

19.4

12

12.9

14.0

15.0

16.0

16.9

16.2

16.9

18.5

19.9

20.6

14

13.8

15.0

16.1

17.2

18.2

16.9

17.7

19.3

20.7

21.5

.

6

11.7

12.6

13.5

14.3

15.1

14.6

15.6

16.4

17.1

17.8

8

13.4

14.6

15.6

16.6

17.2

16.1

17.2

18.1

18.9

19.7

5

10

14.8

16.1

17.0

17.7

18.5

17.2

18.4

19.4

20.2

21.1

12

15.9

17.0

17.9

18.7

19.6

17.5

19.3

20.4

21.4

22.2

14

16.8

17.8

18.7

19.5

20.4

18.2

20.0

21.1

22.2

23.1

6

13.1

14.1

15.2

16.1

17.1

15.9

17.3

17.8

19.1

20.3

8

14.8

16.1

17.3

18.5

19.6

17.3

19.0

19.4

20.9

22.3

6

10

16.2

17.6

19.0

20.1

20.9

18.3

20.2

20.6

22.2

23.8

12

17.2

18.9

20.2

21.2

22.0

19.1

21.1

21.5

23.2

24.9

14

18.1

19.9

21.0

22.0

22.9

19.8

21.9

22.5

24.4

26.2

6

16.0

17.4

19.0

20.0

20.8

18.3

20.1

20.6

21.7

22.6

8

17.7

19.4

20.6

21.7

22.6

19.6

21.6

22.3

23.4

24.5

8

10

19.0

20.5

21.8

23.0

23.9

20.5

22.7

23.4

24.7

25.9

12

19.9

21.4

22.7

23.9

25.0

21.4

23.7

24.3

25.7

26.9

14

20.4

22.0

23.4

24.7

25.8

21.8

24.2

24.9

26.3

27.7

Table 20