FPM, Type A Coils (1/2" DIA.) FPM, Type 5 Coils (5/8" DIA.)

Rows

FPI

400

500

600

650

700

400

500

600

650

700

6

11.2

12.7

14.0

14.6

15.2

15.1

17.0

18.5

19.3

20.0

8

14.2

16.0

17.6

18.3

19.0

18.8

20.9

22.8

23.7

24.5

1

10

17.1

19.2

21.0

21.9

22.7

21.9

24.4

26.6

27.5

28.4

12

19.9

22.3

24.4

25.3

26.2

24.6

27.4

29.9

30.9

31.9

14

22.7

25.4

27.6

28.6

29.6

26.9

30.1

32.7

33.8

34.9

6

20.3

23.3

25.9

27.1

28.3

25.8

29.5

32.6

34.0

35.4

8

25.0

28.6

31.8

33.3

34.7

30.8

35.0

38.8

40.4

42.1

2

10

29.4

33.6

37.3

39.0

40.6

34.7

39.6

43.9

45.8

47.6

12

33.5

38.3

42.5

44.4

46.2

37.8

43.4

48.1

50.3

52.3

14

37.3

42.6

47.3

49.4

51.4

40.4

46.5

51.7

54.2

56.3

6

27.8

32.1

36.0

37.8

39.6

35.2

40.8

45.6

47.9

50.1

8

33.5

38.8

43.5

45.7

47.8

40.1

46.9

52.9

55.7

58.3

3

10

38.4

44.7

50.2

52.7

55.2

43.9

51.6

58.6

61.7

64.8

12

42.8

49.9

56.3

59.2

61.9

46.7

55.3

63.0

66.5

70.0

14

46.7

54.7

61.8

65.0

68.1

48.9

58.2

66.5

70.4

74.1

FPM, Type 5 Coils (5/8" DIA.)

FPM, Type 8 Coils (1" DIA.)

Rows

FPI

400

500

600

650

700

400

500

600

650

700

6

27.4

31.0

34.0

35.4

36.6

23.7

26.7

29.2

30.4

31.5

8

34.3

38.2

41.2

42.4

43.5

30.3

34.0

37.1

38.4

39.7

1

10

39.6

43.2

45.5

46.2

46.7

36.2

40.3

43.7

45.1

46.4

12

43.3

46.1

47.0

56.6

57.9

42.3

46.3

49.2

50.4

51.4

14

45.6

47.0

58.7

59.9

60.8

46.3

50.2

52.9

53.9

54.8

6

49.4

56.6

62.8

65.6

68.3

8

56.9

65.4

72.6

75.7

78.4

2

10

62.8

72.3

79.7

82.7

85.3

12

67.5

77.5

84.8

87.5

89.8

14

71.3

81.4

88.3

90.7

92.4

Ent Air

Average Water Temperature^, °F.

Steam Pressure, PSIG

Temp. °F.

120

130

140

150

160

170

180

190

5

10

20

25

30

40

50

-20

1.077 1.154

1.231 1.308 1.385 1.462 1.538 1.615 1.088 1.142 1.228 1.263 1.295 1.351 1.395

-10

1.000 1.077

1.154 1.231 1.308 1.385 1.462 1.538 1.044 1.098 1.184 1.219 1.251 1.306 1.351

0

0.923 1.000

1.077 1.154 1.231 1.308 1.385 1.462 1.000 1.054 1.140 1.175 1.207 1.262 1.306

10

0.846 0.923

1.000 1.077 1.154 1.231 1.308 1.385 0.956 1.010 1.096 1.131 1.162 1.218 1.262

20

0.769 0.846

0.923 1.000 1.077 1.154 1.231 1.308 0.912 0.966 1.052 1.087 1.118 1.174 1.218

30

0.692 0.769

0.846 0.923 1.000 1.077 1.154 1.231 0.868 0.922 1.007 1.043 1.074 1.130 1.174

40

0.615 0.692

0.769 0.846 0.923 1.000 1.077 1.154 0.824 0.878 0.963 0.999 1.030 1.086 1.130

50

0.538 0.615

0.692 0.769 0.846 0.923 1.000 1.077 0.780 0.834 0.919 0.955 0.986 1.042 1.086

60

0.462 0.538

0.615 0.692 0.769 0.846 0.923 1.000 0.736 0.790 0.875 0.911 0.942 0.998 1.042

70

0.385 0.462

0.538 0.615 0.692 0.769 0.846 0.923 0.692 0.746 0.831 0.867 0.898 0.954 0.998

80

0.308 0.385

0.462 0.538 0.615 0.692 0.769 0.846 0.648 0.702 0.787 0.823 0.854 0.910 0.954

90

0.231 0.308

0.385 0.462 0.538 0.615 0.692 0.769 0.604 0.658 0.743 0.779 0.810 0.866 0.910

100

0.154 0.231

0.308 0.385 0.462 0.538 0.615 0.692 0.560 0.614 0.699 0.734 0.766 0.822 0.866

^ Average water temperature = (entering water temp + leaving water temp) divided by 2.
** For type 5, at 5 PSIG, if (total MBH divided by 0.961) divided by coil tubes is more than to 50 LB per tube, the condensate loading may be too high. At
higher pressures the condensate loading can be more than 50 LB per tube. Get a computer rating for the application.

Table 21

Hot Water

1/2" and 5/8" tube, entering air 60°F. DB

Type A and Type 5, 190°F. average water temperature

^, heating capacities

MBH per SQ FT of coil face area (water velocity=3 fps).

Actual capacity will vary

with coil circuiting and

flow rate

To estimate for other entering air and average water temperatures, multiply by correction factor in
Table 23.

Table 22

Steam

5/8" and 1" tube, entering air 0°F. DB

Type 5*** and Type 8, 190°F. steam at 5 PSIG, heating capacities

MBH per SQ FT of coil face area

Note:

Please contact your representative for ARI ratings for coils. These tables are only estimates.

To estimate for other entering air and steam pressures multiply by correction factor in Table 23.

*Type 8 coils offered as one row
only on model 65 and 75.

Table 23

Capacity connections Factors to Table 21 for other than 60°F. and 190 average water temperature

^

Capcity Correction Facors to Table 22 for other than 0

°F. air and 5 PSIG steam***.