Installer set-up – Honeywell cm921 User Manual

Page 3

Advertising
background image

CM921 CHRONOTHERM

3

EN0H 8557 UK07 R0 09/06

INSTALLER SET-UP

In Installer set-up we can:

❑ Set-up specific applications parameters
❑ Enable special features
❑ Configure system timing master for the zoning system

To enter the installer set-up mode:

a) Move the slider switch to the OFF position.

b) Press and hold the INFO

i

button and the two program

buttons ‘< >’ together.

c) The unit will display the first parameter of installer

parameter group category 1 (from n.1 to n.19).

d) Press the TEMP

or

buttons

to change the factory

setting. The display will flash indicating that a change has
been made.

e) Press the green OK button to confirm this change and the

display will stop flashing.

f) Press

the + button to go to the next parameter.

g) Press the program button

>

to go to category 2 in the

Installer mode (from n.1 to n.14).

h) To exit the installer mode, move the slider switch to the

AUTO or MAN positions.

Abbreviated Set-Up Description

e.g. Cl = Clock Format

Factory Setting or New Choice

Press TEMP

or

to change

e.g. 12 = AM/PM Format

24 = 24hr Format

Installer Set-up Number

(Press

+ or - to change)

e.g. 1 = Clock Format

Brief Description of the
Parameter Function.

Specific Applications

Setting

What do you need to change?

Cycle/
Hour

Minimum
ON time

(in minutes)

Note : All parameters listed below belong to category 2 – System
Parameters (see Installer Parameters Table)

Heating Gas

Boilers

(<30KW)

6

1

No changes required

Oil Boiler

3

4

1. Set Minimum ON Time to 4 minutes.
2. Set Cycle/Hour to 3.

Thermal Actuator

12

1

Set Cycle/Hour to 12.

Zone valve

6

1

No changes required.

Air
conditioning

1. Configure the thermostat to allow switching between heating

and cooling modes (set parameter n.4:HC to 1)

2. Set the thermostat accordingly to the required mode of

operation (heating or cooling) by pressing the TEMP

or

buttons together for 5 seconds.

Modify the cooling program

as required.

Heat Pump/
Air conditioner

3

4

1. Set Minimum ON Time to 4 minutes.
2. Set Cycle/Hour to 3.

Fan coil

6

1

No changes required.