Dimensions – Honeywell cm921 User Manual

Page 5

Advertising
background image

CM921 CHRONOTHERM

5

EN0H 8557 UK07 R0 09/06

DIMENSIONS

Parameter

Installer Set-
Up Number /
Abbreviation
(Press + or -
keys to
select)

Factory Setting

Optional Setting

Category 2 Parameters – System Settings (press the > button to access this category)

Display

Description

Display

Description

Minimum boiler ON
Time

1:Ot

1

1 minute minimum ON time

2 to 5

Selection of 2,3,4 or 5 minutes minimum
ON time

Cycle Rate

2:Cr

6

6 cycles per hour (cph)

3, 9 or12

Selection of 3,9 or 12 cph

Heat / Cool Change

4:HC

0

Disabled

1

Enabled

Pump Exercise

5:PE

0

Pump Exercise Disabled

1

Pump Exercise Enabled

System
Synchronisation

6:Sn

0

Standard operation of the
Room Unit

1

Room unit configured as Synchroniser

Loss of Communication
Instruction

7:LC

0

Relay Off

1

Relay 20% on / 80% off

The following parameters are for the control of other Honeywell Wireless products such as Wireless Underfloor Heating controls and
Wireless Radiator controls. For more information please contact Honeywell sales.

Room Temperature
Sensor Use

8:Su

0

HC60 Control

1,2,3 or 4

1 - HR80/HM80 control with own/remote
sensor (no temperature displayed)

2 - Hr80/HM80/HCE80 control with CM
Sensor

3 - HC60 control and HR80/HM80/
HCE80 control with own/remote sensor

4 – Hr80/HM80/HCE80 control with own/
remote sensor (temperature displayed)

HR80 Window-Open
Function

9:HO 0

Disabled

1

Enabled

HR80 Local Override

10:HL

1

Enabled

0

Disabled

Maximum Flow
Setpoint

11:uF

55

55°C Maximum Flow Temp.

0 to 99

0°C to 99°C adjustments in 1°C steps

Minimum Flow Setpoint

12:LF

15

15°C Minimum Flow Temp.

0 to 50

0°C to 50°C adjustments in 1°C steps

Mixing Value Run Time

13:Ar

150

150 seconds

0 to 240

0 to 240 sec. adjustments in 1sec steps