R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS

15

68-0105—2

Fig. 21. Setting stop in position to restrict low limit setting

to 180°F (82°C) or lower.

Startup

WARNING

Explosion Hazard.

Can cause severe injury, death or property

damage.

Be sure combustion chamber is free of oil or vapor.

1. Push red reset button and release.

2. Open hand valve on oil supply line.

3. Set thermostat to call for heat.

4. Close line switch; burner will start.

5. Under normal conditions, burner operates until

thermostat is satisfied or line switch is opened.

Make certain the system operates as described in the

OPERATION section. Use the following procedure to verify

that the Protectorelay™ burner sequencing relay is controlling

properly.

Flame Failure Check

Shut off the oil supply hand valve while the burner is on. After

45 seconds, the safety switch locks out, the motor stops, and

the oil valve closes. Allow five minutes for the burner to cool,

then manually reset the safety switch.

Ignition Failure Check

Test by closing the oil supply while the burner is off. Run

through the starting procedure but do not open the oil supply

line hand valve. The safety switch locks out as in flame failure.

Then turn the oil back on, and reset the safety switch.

Power Failure Check

Turn off the power supply while the burner is on. When the

burner goes out, restore power and the burner will restart.

NOTE: If operation is not as described, see cover insert for

additional information and check wiring.

Aquastat® Controller Replacement

The Aquastat® limit section of the Protectorelay™ control is

field replaceable. When ordering a replacement assembly,

specify the complete model number of the R8182.

Replace the Aquastat® Limit

1. Disconnect power supply.

2. On all models—Note the position of the connecting

wires.

3. Remove fastening screws and wires.

4. Remove Aquastat® limit and install the new assembly.

MATERIAL SAFETY DATA SHEET (MSDS)

SECTION 1. PRODUCT AND COMPANY

IDENTIFICATION.

Product Name: Heat conductive compound.

MSDS ID: DS9021.

Synonyms: MS1699.

Product Use: Heat conductive material used to enhance

contact and heat transfer in temperature sensor applications.

Manufacturer: Honeywell Inc., 1985 Douglas Drive North,

Minneapolis, MN 55422.

Date Released: October 8, 1999.

Emergency Telephone Information: 1-888-809-3787.

NFPA Ratings:

Health 0; Flammability 1; Reactivity 0; Personal Protection

B.

200

160

140

180

SETTING STOP

STOP ARM
SETTING

PROJECTION "A"

KNOB SET AT 140

°

F (60

°

C)

M4523

1

1

SCALE MARKINGS IN FAHRENHEIT ONLY.

120

Advertising
This manual is related to the following products: