Troubleshooting, Table 1. troubleshooting guide – Honeywell PERFECT WINDOW HR200 User Manual

Page 20

Advertising
background image

APPENDICES

Table 1. Troubleshooting Guide.

Symptom

Cause

Solution

Poor airflow

Plugged outside hood 1/4 in. (6 mm) mesh.

Clean exterior hoods or vents

Filters plugged.

Remove and clean filter.

Core obstructed.

Remove and clean core.

House grilles closed or blocked.

Check and open grilles.

Dampers (if installed) are closed.

Open and adjust dampers

Poor power supply at site.

Have electrician check supply voltage at house.

Ductwork is restricting airflow.

Check duct installation.

Improper speed control setting.

Increase speed of ventilator.

Ventilator airflow improperly balanced.

Have contractor balance ventilator airflow.

Supply air
feels cold

Poor location of supply grilles, airflow can

irritate the occupant.

Locate grilles high on walls or under baseboard

heaters; install ceiling-mounted diffuser or
grilles to avoid blowing directly on occupants
(example: over a sofa).

Outdoor temperature extremely cold.

Turn down ventilator supply speed.

Use a small duct heater (1 kW) to temper the

supply air.
Placement of furniture or closed doors is

restricting movement of air in the home.
If supply air is ducted in furnace return, run

furnace fan continuously to distribute ventilation
air comfortably.

Ventilator airflow can be incorrectly balanced.

Have a contractor balance ventilator airflow.

Dehumidistat
is not
operating

Incorrect connection to external 24-volt control.

Staple/nail is shorting out external low voltage.

Check that correct wires were used.

Check external wiring for a short.

Check dehumidistat setting; it could be at Off.

Set dehumidistat at the desired setting.

Dehumidistat is disabled when the outdoor

temperature is above 60F for 24 hours.

Check the LED on the terminal block for long

flash followed by a short flash.

TROUBLESHOOTING

HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems 68-0171—12

18

Advertising