14

T8621A,C,D

INSTALLATION

Fig. 13—T8621C,D single stage heat pump with cooling changeover. HEAT-AUTO-COOL-OFF system and
AUTO-ON fan switching.

4

5

6

RECOMMENDED INTERCONNECT CABLE: 18-GAUGE THERMOSTAT CABLE,
200 ft. [61 m] MAXIMUM LENGTH. ROUTE INTERCONNECT CABLE AWAY
FROM SOURCES OF ELECTRICAL NOISE.

T8621D ONLY.

DENOTES THERMOSTAT TO SUBBASE INTERCONNECTION.


NOTE: SET CYCLE RATE TO HOT WATER SETTING (3 cph). THERMOSTAT

DOES NOT PROVIDE MINIMUM OFF TIME IN HEATING.

M1548C

SYSTEM
TRANSFORMER

R

C

W1

W2

Y2

Y1

G

RC

FAN RELAY

HIGH
LIMIT

HIGH
LIMIT

L1
(HOT)

L2

HEAT

AUTO

COOL

SYSTEM
SWITCH

AUTO

ON

FAN
SWITCH

1

S1

S2

S3

S1

S2

S3

202905 REMOTE
SENSOR

3

OFF

COMPRESSOR
CONTACTOR

COOLING
CHANGE-
OVER

H1

H2

C1

C2

RELAY K

K

SUBBASE
LOGIC/
CONTROL
CIRCUIT

6

4

5

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.

ADD RELAY (SPDT) TO ACCOMMODATE COOLING CHANGEOVER.

APPLICABLE ONLY ON T8621D MODELS WITH REMOTE SENSOR.

1

2

3

POWER
SUPPLY

THERMOSTAT
LOGIC CIRCUIT

Advertising