Installation, Wiring and electrical, Setting the aquastat – Harman Stove Company SF160 User Manual

Page 7: Optional items, Venting

Advertising
background image



Wiring and Electrical

Following the wiring diagram, run all wires

to their designated connections. Save the main

power for the last hook-up, and leave the breaker

in the off position. The sensor wires attach to the

A350 Controller on the terminals marked “sen”

and “com”. Make sure the sensor is submerged

fully into the well and secured with the set-screws.

Setting The Aquastat

Inside the A350 control, you will see a

square jumper, and a differential dial. Be sure the

jumper is in the “Heating” position. The differen-

tial dial is set to determine how low, below the

temperature set point, you want the water tem-

perature to go before the Automatic Draft Control

opens. A good initial setting for this dial is 5°. Be

sure the 120V wires are attached to the common

and the normally open terminals, and replace the

cover. The external dial is set for the water tem-

perature you wish to maintain, a good setting is

180°.

Inside the Y350 control, ensure that your

wires are connected to the 120VAC terminals,

and replace the cover.

Inside the S350 control, which is used as

overheat protection, you’ll see two dials; offset,

and differential. There is also a jumper which, in

this case, gets placed in the “cooling” position.

The offset dial sets the number of degrees above

the A350 setpoint that you want the overheat

dump to activate. A good set point would be 20°.

That would mean that if the water reaches 200°,

using the A350 setpoint of 180°, the S350 would

close it’s contacts and energize the overheat

dump zone. The differential dial sets the point that

the overheat dump would stop. With the differen-

tial set at 15°, using the temperatures above, the

circuit would re-open, stopping the overheat dump

at a water temperature of 185°. The 120V wiring

is attached on the normally open and the common

position. The normally closed position is not used.

Re-install the covers onto the three Con-

trols.

Optional Items

There is a domestic hot water coil available

for your Trident Boiler. The coil installs in the front

of the boiler, and allows your domestic water to

be heated by the heating system water. Install the

coil now, by removing the round plate and replac-

ing it with the coil and it’s round plate. Be sure to

tighten the bolts evenly, to ensure a good seal.

If electric back-up is desired, install now.

There will be two additional control boxes to add

to your aquastat, which will require the use of

a longer din rail. The two heating elements will

install into the front of the boiler as shown in Fig. 1

FIG.

Venting

The Harman Trident Boiler must be in-

stalled into a chimney approved for solid fuel

burning appliances. In the U.S., the boiler must be

connected to; (1) a prefabricated chimney comply-

ing with the requirements for Type HT chimneys in

the Standard for Chimneys, Factory Built, Resi-

dential Type and Building Heating Appliances, UL

103. Or; (2) a code approved masonry chimney

with a flue liner. In Canada, with prefabricated

chimney systems tested and listed to the High

Temperature Chimney Standard ULC S-629, or

with a code approved masonry chimney. The

minimum recommended height for any chimney

is 16 ft. (4.8m) above the flue collar. Do not re-

duce flue diameter. Nominal size flue is 8 X 8 in.

or equivalent, up to 8 X 12 in. Codes also require

that the chimney must extend a minimum of

Installation

Advertising