Appendix: installation – Hisense Group KFR-3208GW User Manual

Page 25

Advertising
background image

CAUTION

23

Appendix: Installation

5.Air purging
Air and moisture remaining in the refrigerant system have
undesirable effects as indicated below. Therefore, they must be
purged completely.

pressure in the system rises
operating current rises
cooling efficiency drops
moisture in the air may freeze and block capillary tubing
water may lead to corrosion of parts in the refrigerant system

Air Purging with a Vacuum Pump (for Test Run)
(1)Check that each tube (both narrow and wide tubes between

the indoor and outdoor units have been properly connected
and all wiring for the test run has been completed. Note that
both narrow and wide tube service valves on the outdoor
unit are kept closed at this stage.

(2)Using an adjustable wrench or box wrench, remove the valve

caps from the service valve on both narrow and wide tubes.

(3) Connect a vacuum pump and a manifold valve (with

pressure gauges) to the service port on the wide tube
service valve.(Fig.A)

CAUTION

Be sure to use a manifold valve for air
purging. If it is not available, use a
stop valve for this purpose. The ¡°Hi

¡±

k n o b o f t h e m a n i f o l d v a l v e m u s t
always be kept closed.

(4)With the ¡°

Lo¡±

knob of the manifold valve open, run the vacuum

pump. The operation time for the vacuum pump varies with
tubing length and the capacity of the pump. The following table
shows the amount of time for evacuation:

Table

Required time for evacuation when capacity

of 100 liter/h vacuum pump is used

If tubing length is less than 10 m

10 min. or more

15 min. or more

If tubing length is more than 10 m

Be sure to completely insert the hex
wrench before attempting to turn the
valve.

The required time in the above table is calculated based
on the assumption that the ideal (or target) vacuum
condition is around 10 mmHg abs.

(5) With the vacuum pump still running, close the

Lo

knob of the manifold valve. Then stop the vacuum
pump.

(6)With the accessory hex wrench, turn the valve stem on

the narrow tube service valve counterclockwise by 90
degrees (1/4 turn) for 10 seconds, and then turn the
stem clockwise to close it again. (Fig.B)

NOTE

NOTE

(7)Leak test all joints at the tubing (both indoor and outdoors)
with liquid soap. Bubbles indicate a leak. Be sure to wipe off
the soap with a clean cloth.
(8)With the hex wrench, turn the wide tube service valve stem

counter-clockwise to fully open the valve.

(9)Turn the narrow tube service valve stem counter-clockwise

to fully open the valve.

(10)Loosen the vacuum hose connected to the wide tube

service port slightly to release the pressure. Then, remove
the hose.

(11)Replace the bonnet and flare nut on the wide tube service

port and fasten the flare nut securely with an adjustable
wrench or box wrench. Next, mount the valve cap and
tighten it with a torque wrench (the cap needs to be
tightened with the torque of 200kg-cm). This process is
very important to prevent gas from leaking from the system.

(12)Test run the air conditioner.
(13)While the air conditioner is running, apply liquid soap to

check for any gas leaks around the service valves or caps.

(14)If there is no leakage, stop the air conditioner.
(15)Wipe off the soap on the tubing.
This completes air purging with a vacuum pump and
the air conditioner is ready for actual operation.

6. Please contact the technical service for further

information.

Vacuum pump

Indoor unit

Outdoor unit

Lo Hi

Manifold valve

Pressure
gauge

90 (1/4 turn)

Narrow tube

Hex wrench

Wide tube

Valve cap

Vacuum hose to manifold valve

Fig.B

Fig.A

Advertising