Heatiator Heatilator Rave4013i-c User Manual

Page 28

Advertising
background image

Heatilator • RAVE4013I-C • 2293-900 Rev. E • 2/13

28

Figure 7.7

1. Top Vent - Horizontal Termination - (continued)

Top Vent - Horizontal Termination

Venting with 3 elbows

Note: Use SLP Series
components only.

V Minimum

H

1

+ H

2

+ H

3

MAXIMUM

RAVE4013I-C (NG ONLY)

3 ft.

914 mm

15 ft.

4.6 m

H

1

+ H

2

+ H

3

MAX. = 15 ft. (4.6 m)

V

1

MAX. = 7 ft (2.1 m)

V

1

H

1

H

3

H

2

INSTALLED

HORIZONTALLY

INSTALLED

HORIZONTALLY

Note: There MUST be a 25%
reduction in total H when using
fl ex vent except when using the
simple up and out installation
(see Figure 7.3).

CAUTION: The SLP-HRC-SS and SLP-HRC-ZC-SS
termination caps are not approved for use with pro-
pane (LP) fuel. May lead to elevated glass temper-
ature that may cause tempered glass breakage.