OM-356 Page 17

3-9.

Electrical Service Guide

All values calculated at 60% duty cycle.

NOTE

50/60 Hertz Models

Without Power Factor Correction

Input Voltage

200

220

230

400

440

460

520

575

Input Amperes At Rated Output

129

117

112

65

58

56

49

45

Max Recommended Standard Fuse Or
Circuit Breaker Rating In Amperes

175

150

150

80

70

70

60

60

Min Input Conductor Size In AWG/Kcmil

4

4

4

8

8

8

8

10

Max Recommended Input Conductor
Length In Feet (Meters)

111

(34)

134

(41)

146

(45)

196

(60)

238

(72)

260

(79)

332

(101)

273

(83)

Min Grounding Conductor Size In AWG/
Kcmil

6

6

6

8

8

8

10

10

Reference: 1996 National Electrical Code (NEC)

S-0092-J

50/60 Hertz Models

With Power Factor Correction

Input Voltage

200

220

230

400

440

460

520

575

Input Amperes At Rated Output

98

89

85

49

44

43

37

34

Max Recommended Standard Fuse Or
Circuit Breaker Rating In Amperes

150

125

125

70

70

60

60

50

Min Input Conductor Size In AWG/Kcmil

4

4

4

8

8

8

10

10

Max Recommended Input Conductor
Length In Feet (Meters)

117

(36)

141

(43)

154

(47)

204

(62)

246

(75)

269

(82)

230

(70)

281

(86)

Min Grounding Conductor Size In AWG/
Kcmil

6

6

6

8

8

10

10

10

Reference: 1996 National Electrical Code (NEC)

S-0092-J