Model f80a – Fedders F80A User Manual

Page 12

Advertising
background image

11

MODEL F80A

VENT TERMINATION

Terminate all vertical vents with a listed vent cap or roof
assembly unless local codes require otherwise. Locate the
termination in an area free of positive pressure or wind
eddies. Eddies may occur when wind swirls over roof peaks.
They can cause downdrafts and interfere with normal vent
operation.

Some manufactured vent caps are resistant to wind and
eddies; their use is recommended.

The vent termination must be a minimum of 5 feet above
the highest gas appliance connection. The vent must extend
a minimum of 3 feet above the point that it passes through
the roof. The vent termination must be a minimum of 2 feet
higher than any part of the building horizontally within 10
feet of the vent.

DEDICATED VENTING

Figure 7 (below) shows a good method to permit dedicated
venting making use of B-Vent within a masonry chimney.

When using this method, provide support for the B-Vent.

IMPORTANT: maintain at least 1-inch clearance between the
B-Vent and the chimney tile or chimney. This will help
prevent the formation of condensation.

RIDGE

10 FT.

RAIN TIGHT
FLASHING

1" MIN.
CLEARANCE

VENT CAP

5" MIN.

B-1 VENT
RIGID OR
FLEXIBLE

B-1 VENT
ADAPTER

SLOPE UP MIN. 1/4" PER FT.

1" MIN. CLEARANCE
TO COMBUSTIBLES

2 FT.
MIN

3 FT.
MIN

Figure 8: Vent Termination

RIDGE

10 FT.

RAIN TIGHT
FLASHING

1" MIN.
CLEARANCE

VENT CAP

5" MIN.

B-1 VENT
RIGID OR
FLEXIBLE

B-1 VENT
A

SLOPE UP MIN. 1/4" PER FT.

1" MIN. CLEARANCE
TO COMBUSTIBLES

2 FT.
MIN

3 FT.
MIN

FIGURE 7: DEDICATED VENTING

FIGURE 6: VENT TERMINATION

CAUTION

FAILURE TO PROPERLY TERMINATE THE VENT OR
CHIMNEY SYSTEMS COULD ALLOW COMBUSTION
PRODUCTS TO COLLECT INSIDE THE BUILDING CAUSING
PERSONAL INJURY OR DEATH.

Advertising