WARM AIR FURNACE

TROUBLESHOOTING

SEQUENCE OF OPERATION: WHITE RODGERS INTEGRATED FURNACE CONTROL WITH WHITE RODGERS 36G22 GAS VALVE

APPLY POWER TO APPLIANCE

THERMOSTAT CALLS FOR HEAT

AIR PROVING SWITCH PROVED OPEN?

COMBUSTION AIR BLOWER ON

AIR PROVING SWITCH PROVED
CLOSED

PREPURGE

HOT SURFACE IGNITER ON FOR
WARM-UP TIME

MAIN VALVE OPENS

HOT SURFACE IGNITER OFF

MAIN BURNER LIGHTS AND IS
SENSED DURING TRIAL FOR IGNITION?

CIRCULATING AIR FAN ON AFTER DELAY

FLAME SENSE LOST?

MAIN VALVE CLOSES

THERMOSTAT CALL FOR HEAT ENDS

MAIN VALVE CLOSES

COMBUSTION AIR BLOWER OFF
AFTER POST PURGE

CIRCULATING AIR FAN OFF AFTER DELAY

WAIT FOR NEXT CALL FOR HEAT

HOT SURFACE IGNITER OFF

COMBUSTION AIR BLOWER OFF
AFTER POST PURGE

WAIT FOR AIR PROVING SWITCH TO OPEN

FIVE MINUTE WAIT PERIOD

COMBUSTION AIR BLOWER OFF

BETWEEN TRIAL PURGE

MAIN VALVE CLOSES

TRIALS FOR IGNITION LESS THAN FOUR
DURNG THIS IGNITION SEQUENCE?

FLAME SENSE LOST MORE THAN FIVE
TIMES IN THIS CALL FOR HEAT?

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

NO

YES