Fluke 434 User Manual

Page 108

Advertising
background image

Fluke 433/434

Users Manual

21-6

Measurements Measurement

Range Resolution

Accuracy

RMS voltage in Transient
Function

10 ... 1000 Vrms

1 Vrms

± 2.5 % of Vnom

Transient voltage
(TTRANS > 10 µs)

0 ... ± 6000 Vpeak

1 V

± 15 % of meas


Flicker

Settings Adjustment

Range

Resolution

Additional

Information

Steady Voltage
Tolerance

0.0 ... 10.0 % of Vnom

0.1 %

Minimum Steady Time

0.0 ... 10.0 s

0.1 s

Maximum Deviation
Threshold

0.0 ... 10.0 % of Vnom

0.1 %

Measurement Measurement

Range Resolution

Accuracy

PF5

0.00 ... 20.00

0.01

P1min

0.00 ... 20.00

0.01

Pst

0.00 ... 20.00

0.01

Plt

0.00 ... 20.00

0.01

Within ±5 % of tabulated
values according
IEC61000-4-15

Dc

0.0 ... ± 100.0 %

0.1 %

± 1 % (if Umeas

≈ Vnom)

DMAX

0.0 ... ± 100.0 %

0.1 %

± 1 % (if Umeas

≈ Vnom)

TDEX

0.000 ... 9.999 s

10 ms

20 ms (at F = 50 Hz)


CURRENT MEASUREMENTS
Current Inputs

Item Specification

Additional

Information

Nominal input Range

0 - ±5.625 Vpeak

0 - 3.97 Vrms sinewave

Current Clamp Sensitivity

0.1 , 1, 10, 100, 1000 mV/A

variable:

Input impedance

50 k.ohm

Bandwidth >10

kHz

Voltage resolution

1 mV

Advertising
This manual is related to the following products:

433