Trend – Fluke 434 User Manual

Page 49

Advertising
background image

Power & Energy

Trend

11

11-3

To access the Energy popup table:

f

F3


Available function keys:

F2

Pulse count mode on/off.

F3

Switch Energy screen on/off.

F4

Access Trend screen. For description see below.

F5

Switch between HOLD and RUN of screen update.
Switching from HOLD to RUN invokes a menu to select
immediate (NOW) or TIMED start time which allows you
to define start and duration of the measurement.
If Energy is displayed, the readout can be reset with F5.

Trend

To access the Power & Energy Trend screen:

g

F4


The figures in the table are instantaneous values that update constantly. Changes in these

values over time are recorded whenever the measurement is active. All values in the table

are recorded, but the Trends from each row in the table are displayed one at a time. Press

function key F1 to assign the arrow keys to row selection.
The traces build up from the right side. The readings in the header correspond to the most

recent measurements plotted on the right.
In addition to TIMED start of energy usage measurement, the Analyzer can measure

average power during an adjustable time window. Electricity suppliers often bill

industrial customers upon the highest average energy usage during a specified time

window. For this demand interval a period of 15 minutes is common.

For any setting besides OFF horizontal scaling of the trend is fixed so that each data point

corresponds with Max, Min, and Average usage during the interval. The demand interval

can be adjusted between 1 ... 60 minutes or to OFF. The adjustment menu is reached via

the SETUP key and function key F3 – FUNCTION PREF. See Chapter 18, FUNCTION

Advertising
This manual is related to the following products:

433