1750

Operators Manual

12

Installing the Recorder

1. Position the Recorder within 2 m (6 ft) of the monitoring location.
2. The Recorder can be set on the floor or a table, or attached and secured to a pole or other

mounting surface. The Recorder can be oriented vertically or horizontally.

3. Connect the Recorder to a 100 to 240 V ac power source, 50 or 60 Hz.
4. Plug the power cord into a properly-grounded wall outlet.

W

Caution

To avoid damage to the Recorder:

Ground the chassis as appropriate according to your power

connection before you do anything else.

Connect the power cord to the Recorder using the appropriate

supplied adapter.

Connect the power cord to a properly grounded wall outlet.

Be sure to plug the power cord into the Recorder panel BEFORE

connecting it to an outlet.

After a minute, or two, all LEDs should flash ON, then OFF, and then each should turn

ON and OFF in sequence. The LEDs will then remain on if you make secure test lead

connections and there is sufficient voltage and current.

5. Turn on the PDA and tap the Power View icon

to launch Power View.

If a Recorder is within range and is not password protected, it should appear in the drop

down menu just below the main title bar on the PDA. You may need to select Browse for

recorder when first connecting. Select the recorder you want to browse to with the PDA

stylus. Upon selection, the Home screen for live data appears.
If more than one Recorder is within range, these will appear in the drop down menu list.

6. If you have previously established password protection for the Recorder, you must type

the correct password in the Password text box and click OK. (Password protection is

established for a specific Recorder using either the Setup Password menu in Power View

or the Power Analyze software).

Connecting the Recorder to the Wiring

After you have set up the Recorder you are ready to connect the voltage leads and current

probe or flexi-probes to the power network being tested. Refer to the Power Type

diagrams provided on the PDA or in this manual.

XW

Warning

To prevent possible electrical shock, Flexi-probes should not

be applied or removed from hazardous live conductors.

In most cases, you should install the current probes first. Because they are clamped

around wires, current probes are usually more secure than voltage probes. Examine the

conductors you are about to connect to and determine if you should attach the current

probes to the phase wires or busbars before you connect the voltage probes.
1. Select and attach the appropriate current probes to the Recorder.
2. Select and attach the appropriate voltage test leads and probes to the Recorder.