External interface specifications, Environmental and safety specifications – Fluke 1750 User Manual

Page 60

Advertising
background image

1750

Operators Manual

52

Power Factor
Measurement Range .......................................... -1.000 (leading) to 0.000 to +1.000 (lagging)
Measurement Accuracy ......................................

±

1 digit from the calculation of each measured value (

±

3 digits for

total)

Displacement Power Factor
Measurement Method......................................... Calculated from the phase difference between voltage fundamental

and current fundamental

Measurement Range .......................................... -1.000 (leading) to 0.000 to + 1.000 (lagging)
Measurement Accuracy ...................................... ± 0.5 % reading ± 2 % full scale ± 1 digit
Voltage Unbalance and Phase Sequence
Measurement Method......................................... Positive sequence voltage divided by negative sequence voltage, per

IEC 61000-4-30

Harmonic Voltage and Current
Analysis Window................................................. rectangular
Analysis Order .................................................... 1st to 50th order
Measurement Accuracy ...................................... Voltage / Current: 1st to 20th orders: ± 0.5 % reading ± 0.2 % full scale

21st to 50th orders: ± 1 % reading ± 0.3 % full scale (current sensor
accuracy must be included for current and power)

Measurement Method......................................... IEC 61000-4-7:2002
Inter-harmonic Voltage and Current (Intermediate Harmonics)
Analysis Window................................................. rectangular
Analysis Orders .................................................. 0.5 to 49.5th order
Measurement Method......................................... IEC 61000-4-7:2002
Voltage flicker
Measurement Method......................................... as per IEC 61000-4-15:2003: 10 min (Pst), 2 h (Plt)

External Interface Specifications

LAN Interface
Connector ........................................................... RJ-45
Speed and Type ................................................. 10/100 Base-T, auto MDIX
Communications Protocol................................... TCP/IP over Ethernet
Wireless Controller Interface
Connection.......................................................... wireless (2.4 GHz radio)
Speed.................................................................. up to 700 kbit/second
Communications Protocol................................... Bluetooth SPP

Environmental and Safety Specifications

Operating Environment....................................... indoors or in covered area outdoors, up to 2000 m altitude
Storage Temperature and Humidity.................... -20

°

C to 50

°

C, 80 % rh max, non-condensing

Operating Temperature and Humidity ................ 0

°

C to 40

°

C, 80 % rh max, non-condensing

Maximum Rated Working Voltage
Voltage Terminals............................................... 1100 V rms
Voltage Durability................................................ 5550 V rms ac for 1 minute, between voltage input terminals, voltage

input terminals and current probes, and voltage input terminals and
case (50/60 Hz, 1 mA sense current)

Enclosure Protection........................................... IP30 (per EN 60529)
Standards Conformance
EMC .................................................................... IEC 61326-1:2006 Class A

IEC 61000-3-2:2005, 3

rd

Edition

IEC 61000-3-3:2005, 1.2 Edition
AS/NZS 4268:2008 (BT module only)
ETSI EN300328 (V1.7.1:2006)

Safety.................................................................. IEC 61010-1:2001, 2

nd

Edition

Voltage input unit: Contamination Level 2
Overvoltage Category 1000 V CAT III, 600 V CAT IV (anticipated
overvoltage: 8000 V)