Field Controls WML-C User Manual

Page 15

Advertising
background image

30318 R4 9/9/2005

15

Table A-6 Direct Drive Blower Set-Up

Blower Set-Up

Cooling Capacity

0.20 in. w.c.

0.50 in. w.c.

Furnace

Model

Blower

Speed Motor Speed Motor

Tons Power

CFM

Range

WML-60C

GT10 DD

Low

½ HP

Med-Low

½ HP

3

½ HP

763 – 1505

WML-80C

GT10 DD

Med-Low

½ HP

Med-High

½ HP

3

½ HP

763 – 1505

WML-90C

GT10 DD

Med-High

½ HP

High

½ HP

3

½ HP

763 – 1505

MPL-90B

GT12-10DD

Low

¾ HP

Med-High

¾ HP

3

¾ HP

1185 – 1553

MPL-100B

GT12-10DD

Med-High

¾

HP High ¾

HP 3

¾ HP

1185 – 1553

MPL-120B

GT12-10DD

High ¾

HP High ¾

HP 3

¾ HP

1185 – 1553

MPL-130B

GT12-10DD

High ¾

HP High ¾

HP 3

¾ HP

1185 – 1553

Table A-8 Direct Drive Blower Characteristics

CFM

External Static Pressure – Inches w.c.

Furnace

Model

Blower

Motor HP

Motor FLA

∆T Speed

0.20 0.30 0.40 0.50

LOW

813 813 797 763

MED-LOW

1170 1144 1118 1063

MED-HIGH

1423 1381 1291 1220

WML-C

60 - 90

GT10 ½

HP 7.0 45-75°F

HIGH

1505 1444 1359 1291

LOW

1334 1286 1239 1185

MED-LOW

1389 1332 1287 1236

MED-HIGH

1423 1373 1326 1289

MPL-B
90-130

GT12-10DD ¾

HP

12.5

50-80°F

HIGH

1553 1491 1449 1331

TIP:

These Formulae will assist with the design of the ductwork and the determination of airflow delivery:

(

)

(

)

CFM

Bonnet Output

x SystemTemperature Rise

SystemTemperature Rise

Bonnet Output

x CFM

=

=

1085

1085

.

.

Advertising
This manual is related to the following products: