24


IDLE STATE

THERMOSTAT CALLS FOR HEAT

SAFETY CHECK FOR FLAME

(5 SEC.)

BURNER MOTOR & IGNITOR START

SOLENOID VALVE OPENS

TRIAL FOR IGNITION

10 SEC.

BURNER FLAME MONITORED

CARRYOVER STATE

Provides continuous spark

LED diagnostic light ON

Start Carryover Timer

CARRYOVER TIMER EXPIRES

RUN STATE

Igniter turns off.

THERMOSTAT SATISFIED

R7184 SHUTS OFF:

Burner Motor

Solenoid Valve

LED Diagnostic Light

RETURNS TO IDLE STATE

FLAME

FLAME

FLAME

FLAME

NO FLAME

NO FLAME

FLAME LOST

FLAME LOST

REMAINS IN IDLE STATE

R7184

SEQUENCE of

OPERATION

LOCKOUT STATE

R7184:

Shuts off burner motor

Shuts off igniter

Shuts off Solenoid Valve

Fast Flashes LED Diagnostic
Light

TO EXIT LOCKOUT

PRESS RESET

RECYCLE TIMER STARTS

R7184:

Shuts off Solenoid Valve

Shuts off Igniter

Shuts off Burner Motor

Slow Flashes LED
diagnostic light

RECYCLE TIMER EXPIRES

(60 SECONDS

FLAME LOST

SAFETY CHECK FOR FLAME

(5 SEC.)

NO FLAME

FLAME

SAFETY CHECK FOR FLAME

(5 SEC.)

NO FLAME

FLAME