6. WATER SUPPLY - Required Criteria

9. WIRING THE STEAM HUMIDIFIER

7. M OUNTING THE STEAM HUMIDIFIER

8. STEAM OPERATION - Required Criteria

A. WATER SUPPLY USING THE SADDLE VALVE

FURNISHED WITH UNIT. Important! See page 14.

A. INSTALLING AND WIRING THE HUMIDISTAT

B. OVERFLOW & DRAIN LINES - Required Criteria

Installation instructions for the saddle valve are printed on the

plastic bag containing the saddle valve and its components.

Tap into a 1/2” or 3/4” domestic cold water line. Avoid

connecting to water lines from a Reverse Osmosis system or

De-ionized water systems. The supply water must read a

minimum of 25 ppm in order for the Steam unit to reliably

sense the water.

NOTE: Never install the saddle valve on the bottom of the

water pipe. Sediment in the water pipe may clog the saddle

valve. Flush the line before connecting to the unit.

tightening the hex compression nut, tighten only enough to

assure there are no leaks.

NOTE: Saddle valves do not meet plumbing codes in some

areas. A “T” fitting with a valve may be required to meet code

or, if low water pressure causes frequent water alerts on the

steam humidifier. NOTE: Flush the new water line before

connecting it.

NOTE: The use of City water or Municipal water is preferred.

Softened water is preferred over untreated well water. Specify

the Optional WFA-195 disposable water filter for treating

any water supply that is very high in mineral content.

NOTE: Use a water hammer arrester (WH-100) if water

spikes occur (pipes bang)during fill ups.

When

A temperature sensor is mounted in the water reservoir of the

humidifier. As the water temperature increases to about 170

degrees F, the computer closes a set of blower relay contacts to

start the system fan. When the water cools to about 140 degrees

F, the computer will open the relay contacts to shut off the fan.

This operational sequence drastically decreases the chances of

condensation occurring inside the duct-work.

A humidistat, such as the Model #072000 is required to control

the Steam Humidifier. The humidistat may be installed on the

wall in the living space or on the return air duct. NOTE:

Continuos fan operation should be initiated if the humidistat is

installed on the return air duct! Instructions for installation are

packaged with each humidistat. Follow wiring instructions

carefully!

DO NOT connect any foreign voltage to the “H” terminals of the

humidifier! The Humidifier supplies it’s own control voltage.

Simply connect the two “H” terminals straight to any dry contact

humidistat terminals. If you are using a 3rd party Humidistat

that has powered terminals, you must use an isolating relay

to operate the Steam Humidifier. Failure to do so will result

in circuit board failure and will void all warranties.

Schematics on the following pages describe the suggested

interlock wiring arrangement for different HVAC systems.

Interlocking may be performed on systems that provide a 24vac

NEC Class 2 terminal block for system control.

AIR PROVING FEATURE: The Steam Humidifier has an

integrated air proving feature that allows the user to install a sail

switch and/or high humidity switch in the duct and easily

achieve fail safe shutdown in the event of fan/blower failure.

This feature prevents the Steam Humidifier from operating

unless adequate airflow is proven thereby avoiding a saturated

duct condition. WARNING: It is highly recommended to use

an airflow proving device. In particular Duct-Board

applications should always use an airflow proving device.

A factory jumper wire is provided and must be removed when

connecting the sail switch or other field supplied air flow

proving device. Leave the jumper in place if you decide not to

use the airflow proving feature.

IMPORTANT NOTE: If the Steam Humidifier is removed

and disconnected from the system, the blower interlock

circuit must be restored to it's original configuration. Failure

to do so may result in loss of blower operation during cooling

modes!

Use gasket material to seal where the front plate or tank flange

contacts the duct-work. Place the humidifier reservoir into the

opening in the duct and secure with eight (8) sheet metal

screws.

NOTE: If the duct-work will not support the unit in a level

position with the water pan full of water, the duct-work

must be reinforced. Both steam models weigh

approximately 9 Lbs. empty and approximately 15 Lbs.

when full of water.

Because of the high output of this Humidifier, it must not be

operated without the blower operating. The steam

humidifier is designed to be "Dominant" over the HVAC

System Blower. The "System" Blower will be operated by the

humidifier when the water tank temperature reaches 170

degrees F. A minimum of 800 cfm @ 800-900 fpm is required for

proper operation of the steam humidifier. Lower velocities may

result in excessive condensation inside the duct. See Air Proving

Feature on the next column! See Variable Speed on Page 7.

The use of an overflow line and drain line is always required.

Use the supplied 1/2” ID high temperature hose. Slip the hose

over the 1/2” OD “T” drain fitting and use a hose clamp to

secure. Route the hose to a suitable drain, avoiding kinks,

traps and sharp objects. DO NOT route the hose above the

humidifier. Failure to install all necessary drain lines may

result in water leaks during normal operating conditions,

and voids all warranties.

3

B. FIELD WIRING

IMPORTANT: Dedicated fused circuits and outlets of the

proper voltage and current ratings must be provided. Use a

NEMA 5-20R receptacle for the S2000 and a NEMA 6-15R

receptacle for the S2020. All wiring must conform to local and

national codes. Failure to do so will void all warranties.

DO NOT cut off the grounded plug and/or hard wire this unit to

line voltage! DO NOT use extension cords to operate this unit!

Doing so will void all warranties.

When routing the S2000 drain hose into a condensate pump,

be sure to cut the end of the hose at a sharp angle to prevent

the hose from bottoming out in the pan. It could result in

poor draining or no draining at all. Failure to do so may

result in water backing up into the S2000 reservoir and

eventual overflow. See Figure 5.

CORRECT

INCORRECT

X

CONDENSATE

PUMP

DRAIN

HOSE

FIG. 5