Fig. 6, Fig. 8, Control wiring solutions for various hvac systems – Field Controls Electronic Steam Unit - Power S2000 User Manual

Page 4: Fig. 11 4 fig. 7, Fig. 10, Fig. 9

Advertising
background image

Typi ca l

Furnace

S2000 & S2020 Humidifier

Low Voltage Terminal Block

G1 R G2 H

H

Heat only

Thermostat

W

R

G

W

R

Heat Only System and

Steam Humidifier with standard

dry contact Humidistat

Dry Contact

Humidistat

A

A

FIG. 6

Factory

Jumper will

stay in place

unless a field

installed Air

Proving Device

is used.

FIG. 8

Bryant Evolution

Furnace

SPST Dry Contact

Isolating Relay

with 24vac Coil

G1 R G2 H

H

C D

B

A

C D

B

A

Bryant/Carrier Evolution/Infinity

Variable Speed Heat/Cool System

A

A

Model APD or

Equivalent

S2000 & S2020 Humidifier

Low Voltage Terminal Block

2 4 v a c

Common

CONTROL WIRING SOLUTIONS FOR VARIOUS HVAC SYSTEMS

Additional diagram shown on page 7.

blower on the HVAC system does not operate when called

operating the blower on the HVAC system. If the Steam

Humidifier detects a loss of airflow longer than 1 minute, it will

shutdown the heating element and stop producing steam to

across the normally open contacts with the fan/blower running.

fan/blower is running.

062000 Humidistat

G1 R G2 H H

A

A

S2000 & S2020 Humidifier

Low Voltage Terminal Block

Disconnect the wires from the “A”

terminals and check the device & circuit

with a reliable ohm meter. Check continuity

when the fan is off and when it is running.

Model APD current

sensing switch or

equivalent air proving

device. Dry Contacts Close

when fan is running!

00.3

OHM

FIG. 11

4

FIG. 7

Typical Furnace

G1 R G2 H

H

Typical Thermostat

G Y

W

R

G Y

W

R

A

A

S2000 & S2020 Humidifier

Low Voltage Terminal Block

REMOVE

FACTORY

JUMPER

C

C

OD OD C

R

H

H

Outdoor

Temperature

Sensor

072000 Humidistat

Refer to the 072000 Technical Bulletin

Model APD or

Equivalent

FIG. 10

Typical Air Handler

G1 R G2 H

H

Thermostat with built-in

Humidification Control

G Y

W2

R

G Y

W2

R

Heat Pump System and Steam Humidifier with

Combo Thermostat/Humidistat

and Isolating Relay

A

A

S2000 & S2020 Humidifier

Low Voltage Terminal Block

REMOVE

FACTORY

JUMPER

C

H

C

O

O

Outdoor Heat Pump

not shown for clarity

SPST Dry Contact

Isolating Relay

with 24vac Coil

Model APD or

Equivalent

HUM

Bryant

Evolution

Thermostat

DO NOT USE

Program Evolution

T-stat as follows:

1.Heating airflow

To Efficiency mode.

2.Humidifer

installed=Yes

3.Humidify with

Fan=Yes

4. Set FAN to

Continuous Mode &

select MEDIUM

speed.

NOTE: An APD or similar device

must be used in this application.

Wire the APD in series with the HH

circuit.

OD OD C

R

H

H

Outdoor

Temperature

Sensor

072000 Humidistat

Refer to the 072000 Technical Bulletin

FIG. 9

Typical Air Handler

G1 R G2

H

H

Typical Heat Pump

Thermostat

G Y

W2

R

G Y

W2

R

A

A

S2000 & S2020 Humidifier

Low Voltage Terminal Block

REMOVE

FACTORY

JUMPER

C

C

O

O

Outdoor Heat Pump

not shown for clarity

Model APD or

Equivalent

Leave Factory

Jumper in Place

Conventional Heat & Cool System
and Steam Humidifier with 072000

with 072000 Humidistat

Heat Pump System and Steam Humidifier

The latest improvement to the Field Controls humidifiers is the new

“Airflow Interlock Feature” provided on the low voltage terminal

block. Due to popular demand we have made it easier for you to

achieve fail safe lockout in the event the fan or blower on the

HVAC system does not operate when called upon. A high humidity

or airflow proving device is necessary.

You must still determine the type of proving device you want to

use. We recommend our new Model APD switch. But then all you

have to do is connect two low voltage wires from your air proving

device straight to the Steam Humidifier’s “A” terminals. No

additional field relays or components are needed.

The Steam Humidifier monitors the airflow circuit anytime it is

operating the blower on the HVAC system. If the Steam

Humidifier detects a loss of airflow longer than 1 minute, it will

shutdown the heating element and stop producing eam to avoid

saturating the duct.
You must test the air proving device

when you install it to make

sure it will function properly. WARNING: DO NOT

perform this test

with the wires connected to the Steam Humidifier. Temporarily

disconnect them. Refer to Figure 11.

1. After installing the air proving device, test for continuity across
the normally open contacts with the fan/blower off. You should
read infinity (no continuity) when the fan/blower is off.
2. Turn on the fan/blower at the thermostat and test for continuity
across the normally open contacts with the fan/blower running.
You should now read continuity (a complete circuit) when the
fan/blower is running.