5.3

Client Side Map Descriptors

5.3.1 FieldServer Related Map Descriptor Parameters

Column Title

Function

Legal Values

Map_Descriptor_Name Name of this Map Descriptor

Up to 32 alphanumeric characters

Data_Array_Name

Name of Data Array where data is to be
stored in the FieldServer

One of the Data Array names from
Section 4

Data_Array_Offset

Starting location in Data Array

0 to (Data_Array_Length -1) as specified
in Section 4

Function

Function of Client Map Descriptor

Rdbc, Wrbc, Wrbx

5.3.2 Driver Related Map Descriptor Parameters

Column Title

Function

Legal Values

Node_Name

Name of Node to fetch data from

One of the node names specified
in “Client Node Descriptor”
above

Length

Length of Map Descriptor

See Map Descriptor Example for
recommended lengths

Met1_Function

Specify the function. Additional notes and
explanations are provided in the examples. Refer
also to Appendix B.3

Hold Time, Mode, Count, Device
Select,

Current

Record,

SubDevice/Port Select

DA_Byte_Name*

A secondary Data Array is specified using this
parameter. The driver stores the read current
record response byte for byte in the secondary
Data Array.

One of the Data Array names
from Section 4

Met1_SubDev_or_Port*

This parameter must be specified in conjunction
with the Address Parameter if a SubDevice or Port
is being polled.

Device, SubDevice, Port

Address*

This parameter is used to specify the SubDevice or
Port number if either is being polled.

Port numbers: 0-63 SubDevice
numbers: 1-64

Met1_Label*

A method of storing count data using a 3-character
label. Use of this parameter to allows the driver to
know which count to store. Refer to example in
Section 5.12

Any

3

character

label

programmed by the user to
identify the sample point – e.g.
0.1
LOC, FLO, DATETIME.

5.3.3 Timing Parameters

Column Title

Function

Legal Values

Scan_Interval Rate at which data is polled ≥0.001s