2.6 Electrical interface

The Local alarm (1060-024) requires power connections as follows: (See appendix A for
the 1060-13 and 1060-024 drawings)
Terminate the input power to TB2-1(L1) of the Local alarm assembly at the end of
this installation .

1. Earth ground to chassis lug items 17 and 18 in view A-A of the local alarm

assembly.

2. The L2 neutral connection (white) to TB1-8.
3. Connect the 75 foot power interface (male end) cables (1060-022 ) to both J1

and J2 . They are interchangeable.

4. Remove the dust cap and connect the 1060ds-24 ten foot cable assembly to
J3 and connect the free end to the I/O connector on the 1060am-nm-LR .

The Remote alarm (1060-034) require power connections as follows: .(See appendix A
for the 1060-023 and 1060-034 drawings)

1. Earth ground to chassis lug items 21 and 22 in view A-A of the remote alarm

assembly.

2. The L2 neutral (L2) connection (white) to TB1-8.
3. Connect either female end of the power interface cable to P1 on the remote

alarm chassis .

The Flasher alarm (1060-026) requires power connections as follows:
(see appendix A for 1060-033 and 1060-026 drawings)

1. Earth ground to chassis lug of the flasher alarm assembly.
2. Neutral (L2) connection to ac-flasher terminal 1.
3. Connect the remaining female end of the power interface cable to P1.