Friedrich CP14-18-24 CP24N30 User Manual

Page 16

Advertising
background image

16

Problem

Possible Cause

Action

Water "spitting"

into room

Sublimation: When
unconditioned saturated, outside air mixes with
conditioned air, condensation forms on the cooler
surfaces

Ensure that foam gaskets are installed in between
window panes & in between the unit & the sleeve.
Also, ensure that fresh air/exhaust vents (on
applicable models) are in the closed position & are
in tact

Downward pitch of installation is too steep

Follow installation instructions to ensure that
downward pitch of installed unit is no less than 1/4"
& no more than 3/8"

Restricted coil or dirty fi lter

Clean & advise customer of periodic cleaning &
maintenance needs of entire unit

Problem

Possible Cause

Action

Excessive moisture

Insuffi cient air circulation thru area to be air
conditioned

Adjust louvers for best possible air circulation

Oversized unit

Operate in "MoneySaver" position

Inadequate vapor barrier in building structure,
particularly fl oors

Advise customer

Problem

Possible Cause

Action

T-stat short cycles

T-stat differential too narrow

Replace t-stat

Plenum gasket not sealing, allowing discharge air to
short cycle t-stat

Check gasket. Reposition or replace as needed

Restricted coil or dirty fi lter

Clean & advise customer of periodic cleaning &
maintenance needs of entire unit

Problem

Possible Cause

Action

Prolonged off cycles

(automatic operation)

Anticipator (resistor) wire disconnected at t-stat or
system switch

Refer to appropriate wiring diagram

Anticipator (resistor) shorted or open

Disconnect plus from outlet. Remove resistor from
bracket. Insert plug & depress "COOL" & "FAN
AUTOMATIC" buttons. Place t-stat to warmest
setting. Feel resistor for temperature. If no heat,
replace resistor

Partial loss of charge in t-stat bulb causing a wide
differential

Replace t-stat

Problem

Possible Cause

Action

Outside water leaks

Evaporator drain pan cracked or obstructed

Repair, clean or replace as required

Water in compressor area

Detach shroud from pan & coil. Clean & remove old
sealer. Reseal, reinstall & check

Obstructed condenser coil

Use pressure wash or biodegradable cleaning agent
to clean

Fan blade/slinger ring improperly positioned

Adjust fan blade to 1/2" of condenser coil

Cooling Only Room Air Conditioners: Troubleshooting Tips