5.3.

Server Side Map Descriptors

5.3.1.

FieldServer Specific Map Descriptor Parameters

Column Title

Function

Legal Values

Map_Descriptor_Name Name of this Map Descriptor

Up to 32 alphanumeric
characters

Data_Array_Name

Name of Data Array where data is to be
stored in the FieldServer

One of the Data Array
names from “Data Array”
section above

Data_Array_Offset

Starting location in Data Array

0 to maximum specified
in “Data Array” section
above

Function

Function of Server Map Descriptor

Server

Server_Hold_Timeout

Specifies time FieldServer will reserve
Server side connection while waiting for
the Client side to update data in
Data_Array (if necessary)

>1.0s

5.3.2.

Driver Specific Map Descriptor Parameters

Column Title

Function

Legal Values

Node_Name

Name of Node to fetch data from

One of the Node
names specified in
“Client

Node

Descriptor” above

SCS128_Poll_Type

Specify type of requests to handle from client.
‘Indications’ Handle all read requests from client.
‘Controls’ Handle all write requests from client

Indications, Controls

Data_Type

‘Flag’ each byte of Controls will be stored in 8
consecutive locations in the Data Array.
Similarly while responding Indications; status
byte will be composed with data from 8
consecutive locations.
‘Byte’ each byte of Controls will be stored as 8
Bit Integer at specified location. Similarly while
responding Indications; status byte will be
composed with data from single location.
‘Register’ every two bytes of Controls will be
stored as 16 Bit integer at specified location.
Similarly while responding indications; two
Control bytes will be composed with data from
single location.
’32-Bit_Reg’ every four Control bytes will be
stored as 32 Bit integer at specified location.
Similarly while responding indications; four
Control bytes will be composed with data from
single location.
Refer to Appendix A

Flag, Byte, Register,
32-Bit_Reg

Length

Length of Map Descriptor
Number of indications to serve or number of
controls to store as per Data_Type.

Flag: 8-256, 16
Byte: 1-32, 2
Register: 1-16, 1
32-Bit_Reg: 1-8, 1

Address

Irrelevant parameter for this driver

Advertising