FieldServer Safetran FS-8700-128 User Manual

Page 8

Advertising
background image

FS-8700-128 Safetran SCS-128 Manual

Page 8 of 15

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: [email protected]

4.4.

Client Side Map Descriptors

4.4.1.

FieldServer Related Map Descriptor Parameters

Column Title

Function

Legal Values

Map_Descriptor_Name Name of this Map Descriptor

Up

to

32

alphanumeric

characters

Data_Array_Name

Name of Data Array where data
is to be stored in the FieldServer

One of the Data Array names
from “Data Array” section above

Data_Array_Offset

Starting location in Data Array

0 to maximum specified in “Data
Array” section above

Function

Function of Client Map Descriptor

Rdbc, Wrbc, Wrbx

4.4.2.

Driver Related Map Descriptor Parameters

Column Title

Function

Legal Values

Node_Name

Name of Node to fetch data from

One

of

the

Node

names

specified

in

“Client

Node

Descriptor” above

SCS128_Poll_Type*

Specify Poll_type
‘Recall’ or 2 always poll for current indications
‘Poll’ or 1 request for indications if changed
‘Controls’ or 3 writes controls to target device
‘Cutoff’ or 5 or 6 send ‘cutoff’ command to
target device

For

Read

Map

Descriptors :
Recall, 2, Poll, 1,
For

Write

Map

Descriptors :
Controls, 3
Cutoff, 5, 6

Data_Type*

‘Flag’ - each byte of Indication statuses will be
stored in 8 consecutive locations in the Data
Array. On write; one Control byte will be
composed from 8 consecutive locations.
‘Byte’- each byte of Indication statuses will be
stored as an 8 Bit Integer at the specified
location. On Write; one Control byte will be
composed from a single location.
‘Register’ - two bytes of Indication statuses will
be stored as a 16 Bit integer at the specified
location. On Write; two Control bytes will be
composed from a single location.
’32-Bit_Reg’ four bytes of Indication statuses
will be stored as 32 Bit integers at the
specified location. On Write, four Control bytes
will be composed from a single location.
Refer to Appendix A

Flag, Byte, Register,
32-Bit_Reg

Length*

Length of Map Descriptor
Number of indications to store or number of
controls to write as per Data_Type.

Flag: 8-256, 16
Byte: 1-32, 2
Register: 1-16, 1
32-Bit_Reg: 1-8, 1

4.4.3.

Timing Parameters

Column Title

Function

Legal Values

Scan_Interval

Rate at which data is polled

≥0.001s

Advertising