FieldServer Safetran FS-8700-128 User Manual

Page 7

Advertising
background image

FS-8700-128 Safetran SCS-128 Manual

Page 7 of 15

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com

Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: [email protected]

4.2.

Client Side Connection Descriptions

Section Title

Connections

Column Title

Function

Legal Values

Port

Specify which port the device is connected
to the FieldServer

P1-P8

1

Protocol

Specify protocol used

SCS-128
SCS128
Safetran SCS-128

Baud*

Specify baud rate

75, 150, 300 ,600, 1200, 2400, 9600
(Vendor limitation)

Parity*

Specify parity

Even (Vendor limitation)

Data_Bits*

Specify data bits

8 (Vendor limitation)

Stop_Bits*

Specify stop bits

1 (Vendor limitation)

Handshaking* Specify hardware handshaking

None

Poll_Delay*

Time between internal polls

0-32000 seconds, 0.05 seconds

Example

//

Client Side Connections


Connections
Port,

Protocol,

Baud,

Parity,

Handshaking,

Poll_Delay

P8,

SCS-128,

9600,

Even,

None,

0.100s

4.3.

Client Side Node Descriptors

Section Title

Nodes

Column Title

Function

Legal Values

Node_Name

Provide name for Node

Up to 32 alphanumeric
characters

Node_ID

SCS-128 station address of physical Server Node

1-127

Protocol

Specify protocol used

SCS-128
SCS128
Safetran SCS-128

Connection

Specify which port the device is connected to the
FieldServer

P1-P8

1

SCS128_Ack*

If ON, Ack will be sent to Server upon receipt of every
indication response

OFF, ON

Example

// Client Side Nodes

Nodes

Node_Name,

Node_ID,

Protocol,

Connection,

SCS128_Ack

NODE_A,

1,

SCS-128,

P8,

OFF

1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware.

Advertising