Fireplace installation, Minimum clearance to combustibles, Framing – FMI (V)3612ST User Manual

Page 4: Selecting location

Advertising
background image

www.fmiproducts.com

115603-01D

4

Fireplace inSTallaTion

MINIMUM CLEARANCE TO

COMBUSTIBLES

Back and sides of fireplace

1/2" min.

Adjacent wall

12" min.

Chimney outer pipe surfaces

2" min.

Bottom of fireplace to floor

0" min.

WARNING: Do not block

required air spaces with insu-

lation or any other material. Do

not obstruct effective opening of

fireplace with any type of facing

material. Combustible material

must not be in contact with black

front face of fireplace.

Figure 2 - Common Location of Fireplace

FRAMING

1. Frame the opening for the fireplace using

the dimensions shown in Figures 4 and 5

and Figure 6 on page 5.

39

3

/

4

"

(101cm)

Min.

43

1

/4"

(109.8cm)

23

5

/

8

"

(60cm)

Figure 4 - Framing Firebox

1" MIN (2.5cm) TO

COMBUSTIBLES

15" DIA.

O.D.

(38.1cm)

OUTER

PIPE

21

5

/

16

"

(54.1cm)

42

5

/

8

"

(108.2cm)

12"

(30.4cm)

24"

(60.9cm)

2" (5cm) MIN.

CLEARANCE

FROM OUTER PIPE

TO COMBUSTIBLES

Figure 5 - Framing Clearances

Spacers on Sides of Fireplace
Provide Required 1" (2.5 cm)
Clearance

2" (5 cm) Min. Clearance
From Pipe to Combustibles

3" (7.6 cm)

12" (30.4 cm) Min. From Perpendicular
Side Wall to Fireplace Opening (Typ.)

Figure 3 - Fireplace Clearances

SELECTING LOCATION

To determine the safest and most efficient

location for the fireplace, you must take into

consideration the following guidelines:
1. The location must allow for proper clear-

ances (see Figure 2).

2. Consider a location where the heat output

will not be affected by drafts, air condition-

ing ducts, windows or doors.

3. A location that avoids the cutting of

joists or roof rafters will make installation

easier.

4. If an outside air kit is to be installed, ac-

cessibility to outside combustion air must

be considered. This can also be achieved

through a vented crawl space in some

cases (see Optional Outside Air Kit on

page 6).

The typical installation for a (V)3612ST is a

projected installation which allows you to ex-

tend the fireplace any distance into the room.

A projection may be ideal for a new addition

on an existing, finished wall.

Advertising