FS-8700-47 DNP 3.0 Driver Manual

Page 36 of 51

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Appendix A.10. Controlling the DNP 3.0 Driver’s Function Code

When a write Map Descriptor is found by the DNP 3.0 Driver it will use the DNP protocol’s write
function to write data to the DNP device. If the DNP device’s vendor requires that an alternative DNP
function be used, use the keyword dnpFunction in the Map Descriptor and specify the function that
the vendor requires (provided that it is in the list of functions implemented by this driver.)

Example: To set a Control Relay Output Descriptor’s state in a SEL-351A relay you cannot use a
write function. The vendor requires you use functions 3, 4, 5 or 6. Select the appropriate function and
specify it as the value of the dnpFunction parameter.

In some cases the DNP 3.0 driver will change the default function automatically. This will be
reported in the error log.

The dnpFunction parameters may have any legal DNP protocol function. The function must be
specified as a decimal value.

Function

Value for
dnpFunction

Client Supports Server Supports

Confirm

0

Yes

Yes

Read

1

Yes

Yes

Write

2

Yes

Yes

Select

3

Yes

5

Yes

5

Operate

4

Yes

5

Yes

5

Direct Operate

5

Yes

5

Yes

5

Direct Operation with no Ack

6

Yes

5

Yes

5

Immediate freeze

7

Immediate freeze with no Ack

8

Limited*

Freeze Clear

9

Freeze Clear with no Ack

10

Limited*

Freeze Time

11

Freeze Time with No Ack

12

Cold Restart

13

Warm Restart

14

Delay Measurement

23

Yes

Yes

When the Function #23 (Delay Measurement) is used the following two notes apply:
1. When the driver is configured as a Client, the configuration must also specify the dnpDataType

parameter set to Object 52 (Time Delay Objects) and the dnpDataVari parameter to variation 2
(Time Delay Fine ). The driver reads the single object from the Server. The address parameter is
ignored.

2. When the driver is configured to serve a response to a poll with application function #23 then the

configuration must have a Server Map Descriptor with dnpDataType parameter set to Object 52
(Time Delay Objects) and dnpDataVari parameter set to variation 2 (Time Delay Fine ). The
address parameter is ignored as the poll is for a single object. The driver responds by serving
data from the Data Array element specified on the Server Map Descriptor – most DNP 3.0 RTU
devices respond by reporting the number of milliseconds between receiving the 1

st

bit of the poll

and sending the 1

st

bit of the response.


5

There are limitations to the Select and Operate Functionality. Refer to Appendix A.19 for more

information.