FS-8700-47 DNP 3.0 Driver Manual

Page 44 of 51

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

considered to be selected and the operation can proceed. If the value is zero, the driver rejects the
command. If the secondary Data Array is not specified, the port is considered to be permanently
selected.

The driver supports the following Control Codes

Code Operation Supported
0

Null

No

1

Pulse On

No

2

Pulse Off

No

3

Latch On

Yes

4

Latch Off

Yes

5-15

Undefined

N/A



‘Direct Operate’ and ‘Direct Operate with No Acknowledgement’ Commands
The driver does not check if the data object had previously been selected. The supported Control
Codes are described above.

Analog Output Block
When a ‘Select’ command is received the driver sets the select flag in a secondary Data Array
defined by the “DA_Bit_Name” parameter, if available. When any of the operate commands are
received the driver stores the value sent with the command in the Data Array defined on the Map
Descriptor.

Control Relay Block (Object=12)
If the Control Code is supported the driver does the required action.

The driver supports the following Control Codes

Code Operation Supported
0

Null

Not Supported

1

Pulse On

Not Supported

2

Pulse Off

Not Supported

3

Latch On

Driver sets Data Array value to ‘1’

4

Latch Off

Driver sets Data Array value to ‘0’

5-15

Undefined

N/A


If the “DA_Bit_Name” parameter is specified then the driver stores the control code as extracted from
the command and if the “DA_Byte_Name” is specified then the driver stores the count field, extracted
from the command message.

Pattern Control Block
Object 12 variations 2 & 3 are not supported by the driver.