FieldServer FS-8700-47 User Manual

Page 9

Advertising
background image

FS-8700-47 DNP 3.0 Driver Manual

Page 9 of 51

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

4.2.

Client Side Connection Descriptors

Section Title
Connections
Column Title

Function

Legal Values

Port

Specify which port the device is connected to the
FieldServer

P1-P8, R1-R2

1

Baud*

Specify baud rate

110 – 115200, standard
baud rates only

Parity*

Specify parity

Even, Odd, None, Mark,
Space

Data_Bits*

Specify data bits

7, 8

Stop_Bits*

Specify stop bits

1

Protocol

Specify protocol used

DNP

Handshaking* Specify hardware handshaking

None

Poll Delay*

Time between internal polls

0-32000 seconds, 1
second.

Application*

Versions of the driver prior to 1.02a used a different
method to calculate DA offset. Refer to Appendix A.16.

It is also possible to use this parameter to control if link
resets are used/required. Refer to Appendix A.15.

OriginalStyle,
NoLink,
OrigStyle-NoLink

Example

// Client Side Connections

Connections

Port

,Baud ,Parity ,Protocol ,Handshaking ,Poll_Delay

R1

,9600 ,None

,DNP

,None

,0.100s

4.3.

Client Side Node Descriptors

Section Title

Nodes

Column Title

Function

Legal Values

Node_Name

Provide name for node

Up

to

32

alphanumeric

characters

Node_ID

DNP 3.0 station address of physical Server
node

0-65535

Protocol

Specify protocol used

DNP

Port

Specify which port the device is connected to
the FieldServer

P1-P8, R1-R21

Example

// Client Side Nodes

Nodes

Node_Name ,Node_ID ,Protocol ,Port
PLC 1

,1

,DNP

,P1

1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware.