Server side connection parameters – FieldServer Canatal Satchnet Driver FS-8700-59 User Manual

Page 11

Advertising
background image

FS-8700-59 Canatal Driver Manual

Page 11 of 19

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

6

CONFIGURING THE FIELDSERVER AS A CANATAL SATCHNET PROTOCOL DRIVER
SERVER

For a detailed discussion on FieldServer configuration, please refer to the instruction manual for the FieldServer.
The information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See “.csv” files on the driver diskette).

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate
with a Canatal Satchnet Server.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for (Driver Name) communications, the driver independent FieldServer buffers need to be declared
in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes”
section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section.
Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

6.1

Server Side Connection Parameters

Section Title
Connections
Column
Title

Function

Legal Values

Port

Specify which port the device is connected to the
FieldServer

P1-P8, R1-R2

4

Baud*

Specify baud rate

1200, 2400, 4800, 9600 (Vendor
limitation)

Parity*

Specify parity

Even

Data_Bits*

Specify data bits

7

Stop_Bits*

Specify stop bits

1

Protocol

Specify protocol used

Canatal, Satchnet


Example

// Server Side Connections

Connections

Port

, Baud

, Parity

, Protocol

, Data_Bits

, Stop_Bits

R1

, 1200

, Even

, Canatal

, 7

, 1

4

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available

on specific hardware.

Advertising