Appendix C. Reference

Appendix C.1. Canatal Device Data Tables

Canatal Devices have their data organized into data tables. A query requests a number of elements from a
particular data table. The number, length and content of data tables vary according to the series number of the
device being addressed. The following series and tables are supported by this driver.

Note that for Canatal firmware revisions from 2002 onwards, “Time” data available in Table 13 is now available in
Table 69, and Table 13 has been made obsolete.

Table Data Format

Max Elements Read/Write Description

Notes

Series 2

4

CANA_BCD_CODED 6

R

FirmWare

5

CANA_FLOAT

34

RW

Keycode

6

CANA_FLOAT

6

R

Sensor Reading

7

CANA_FLOAT

3

RW

Security

8

CANA_BYTE

84

RW

Time Schedule

9

CANA_BYTE

2

R

Switched Output

10

CANA_PERCENT

6

R

Analog Outputs

11

CANA_BYTE

19

RW

Alarm Status

12

CANA_BYTE

1

R

Control Status

13

CANA_BCD_CODED 7

RW

Time

14

CANA_BYTE

4

R

Staged Output Status

15

CANA_BYTE

1

RW

Plant Status

Series 4

4

CANA_BCD_CODED 6

R

FirmWare

5

CANA_FLOAT

34

RW

Keycode

6

CANA_FLOAT

6

R

Sensor Reading

7

CANA_FLOAT

3

RW

Security

8

CANA_BYTE

1

R

Switched Output

9

CANA_PERCENT

5

R

Analog Outputs

10

CANA_BYTE

16

RW

Alarm Status

11

CANA_BYTE

1

R

Control Status

12

CANA_BYTE

4

R

Staged Output Status

13

CANA_BYTE

1

RW

Plant Status

Series 5

4

CANA_BCD_CODED 6

R

FirmWare

5

CANA_SWAP_INT 100

RW

Keycode

6

CANA_BYTE

4

R

Sensor Reading

7

CANA_SWAP_INT 3

RW

Security

8

CANA_BYTE

84

RW

Time Schedule

9

CANA_BYTE

3

R

Switched Output

10

CANA_PERCENT

4

R

Analog Outputs

11

CANA_BYTE

48

RW

Alarm Status

12

CANA_BYTE

3

R

Control Status

13

CANA_BCD_CODED 7

RW

Time

14

CANA_BYTE

4

R

Staged Output Status

15

CANA_WORD

17

RW

Accumulating Run Time

15

CANA_BYTE

1

RW

Machine Remote Control

Series 6 & Series 8

Advertising