Appendix c. reference, Appendix c.1. canatal device data tables, To appendix c.1 – FieldServer Canatal Satchnet Driver FS-8700-59 User Manual
Page 18: Appendix c.1

FS-8700-59 Canatal Driver Manual
Page 18 of 19
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Appendix C. Reference
Appendix C.1. Canatal Device Data Tables
Canatal Devices have their data organized into data tables. A query requests a number of elements from a
particular data table. The number, length and content of data tables vary according to the series number of the
device being addressed. The following series and tables are supported by this driver.
Note that for Canatal firmware revisions from 2002 onwards, “Time” data available in Table 13 is now available in
Table 69, and Table 13 has been made obsolete.
Table Data Format
Max Elements Read/Write Description
Notes
Series 2
4
CANA_BCD_CODED 6
R
FirmWare
5
CANA_FLOAT
34
RW
Keycode
6
CANA_FLOAT
6
R
Sensor Reading
7
CANA_FLOAT
3
RW
Security
8
CANA_BYTE
84
RW
Time Schedule
9
CANA_BYTE
2
R
Switched Output
10
CANA_PERCENT
6
R
Analog Outputs
11
CANA_BYTE
19
RW
Alarm Status
12
CANA_BYTE
1
R
Control Status
13
CANA_BCD_CODED 7
RW
Time
14
CANA_BYTE
4
R
Staged Output Status
15
CANA_BYTE
1
RW
Plant Status
Series 4
4
CANA_BCD_CODED 6
R
FirmWare
5
CANA_FLOAT
34
RW
Keycode
6
CANA_FLOAT
6
R
Sensor Reading
7
CANA_FLOAT
3
RW
Security
8
CANA_BYTE
1
R
Switched Output
9
CANA_PERCENT
5
R
Analog Outputs
10
CANA_BYTE
16
RW
Alarm Status
11
CANA_BYTE
1
R
Control Status
12
CANA_BYTE
4
R
Staged Output Status
13
CANA_BYTE
1
RW
Plant Status
Series 5
4
CANA_BCD_CODED 6
R
FirmWare
5
CANA_SWAP_INT 100
RW
Keycode
6
CANA_BYTE
4
R
Sensor Reading
7
CANA_SWAP_INT 3
RW
Security
8
CANA_BYTE
84
RW
Time Schedule
9
CANA_BYTE
3
R
Switched Output
10
CANA_PERCENT
4
R
Analog Outputs
11
CANA_BYTE
48
RW
Alarm Status
12
CANA_BYTE
3
R
Control Status
13
CANA_BCD_CODED 7
RW
Time
14
CANA_BYTE
4
R
Staged Output Status
15
CANA_WORD
17
RW
Accumulating Run Time
15
CANA_BYTE
1
RW
Machine Remote Control
Series 6 & Series 8