Editing parameters – GE EX2100 User Manual

Page 86

Advertising
background image

5-10

••••

Chapter 5 Diagnostic Interface-Keypad

GEH-6632 EX2100 User’s Guide

2. To view detail on a particular fault, select that fault (listed on the Active Fault

Display screen). The following screen displays.

SELECTED FAULT - PRESS

Low AC V, B

006:40:11.008

Low AC input volts detected on
the field exciter.

3. Reset the faults either of two ways:

- Select Reset Faults Now in the Fault Display screen.
- Press the Reset Faults button.

Ø To view the exciter’s Fault History (a list of previously cleared faults

and fault resets)

This display list may be
multiple screens long.

•

From the Main Menu, select Fault List, then select Display Fault History.

FAULT HISTORY DISPLAY

0 Cleared

Fault reset

86

Trip

DC Over-current trip.

115 Trip

Bridge 1 Fan 1 BAD

58 Brief

Low AC V

95

Field temp alarm

--- RESET FAULTS NOW ---

Editing Parameters

There are two types of parameters that can be changed using the keypad:

•

Option parameters lists items (options) for you to select. For example,

True/False is an option parameter.

•

Numeric parameters lists valid digits that you select to create a number.

Ø To edit a parameter
1. From an exciter Parameters screen, select the parameter that is to be changed.

Parameters

GPT_Vrms

=

<No Value>

VHiTripLev

=

1.2

AFFL

=

100

VFFL

=

100

100.0

TripVHiTrip

=

Trip enabled

This displays either an Option or Numeric parameter screen (see both below) with
the New Value line highlighted.