APPENDIX A BLOWER PERFORMANCE TABLES

DIRECT DRIVE

STANDARD CPC/H060 DOWN SHOT

SPEED

TAP

EXTERNAL STATIC

PRESSURE (ESP)

in w.c.

STANDARD

CFM

AMPS

WATTS

RPM

0.10

1334

1.65

180

627

0.20

1286

1.75

192

665

0.30

1212

1.83

202

715

0.40

1144

1.94

216

759

0.50

1077

1.99

222

792

0.60

1039

2.10

238

830

0.70

953

2.17

248

874

0.80

904

2.27

258

913

0.90

825

2.30

266

940

0.10

1512

2.12

240

682

0.20

1469

2.24

254

720

0.30

1397

2.31

264

759

0.40

1333

2.44

282

803

0.50

1285

2.54

296

836

0.60

1221

2.59

304

874

0.70

1173

2.72

322

913

0.80

1118

2.77

328

946

0.90

1049

2.90

344

984

0.10

2053

4.27

540

869

0.20

2014

4.39

558

896

0.30

1999

4.60

576

929

0.40

1947

4.68

588

957

0.50

1897

4.79

608

989

0.60

1857

4.87

620

1012

0.70

1763

4.99

640

1050

0.80

1741

5.06

650

1072

0.90

1669

5.19

668

1105

0.10

2137

4.95

634

913

0.20

2093

5.07

652

940

0.30

2095

5.19

670

962

0.40

2026

5.28

682

990

0.50

1980

5.40

698

1018

0.60

1961

5.49

720

1039

0.70

1914

5.58

732

1072

0.80

1845

5.70

742

1100

0.90

1766

5.69

740

1127

0.10

2299

5.70

742

942

0.20

2233

5.80

748

969

0.30

2217

5.90

768

990

0.40

2157

6.07

786

1018

0.50

2131

6.12

804

1045

0.60

2060

6.21

816

1073

0.70

2015

6.30

820

1095

0.80

1940

6.27

816

1111

0.90

1862

6.13

790

1128

NOTES:

T5

CPC/H060 DIRECT DRIVE DOWN SHOT

Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM
correction for wet coil = 4 %. 5 Ton models are shipped from the factory with speed tap set on T4.

T1

T2

T3

T4