Inspect curb to ensure that none of the utility services (elec-
tric) routed through the curb protrude above the curb.

I

F

PROTRUSIONS

EXIST

,

DO

NO

ATTEMPT

TO

SET

UNIT

ON

CURB

.

CAUTION

ROOF TOP DUCT CONNECTIONS

Install all duct connections on the unit before placing the unit
on rooftop.

H

ORIZONTAL

D

ISCHARGE

For horizontal discharge, remove the supply and return duct
covers and place them over the vertical discharge return and
supply openings. Install with insulation facing up, using the
longer screws provided in the literature package.

Ensure that the top of the duct connection frame is flush with
the top of the roof curb.

Flexible duct connectors between the unit and ducts are rec-
ommended. Insulate and weatherproof all external ductwork
and joints as required and in accordance with local codes.

RETURN

SUPPLY

12”

17”

7 3/8”

11”

4 7/8””

25”

6 3/16”

REMOVE

COVERS

HORIZONTAL DISCHARGE DUCT CONNECTIONS

RIGGING DETAILS

WARNING

T

O PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT

POSITION DURING ALL RIGGING AND MOVING OPERATIONS.

T

O FACILITATE

LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN
ADEQUATE CABLE SLING.

I

F

UNITS

ARE

LIFTED

TWO

AT

A

TIME

,

THE

FORK

HOLES

ON

THE

CONDENSER

END

OF

THE

UNIT

MUST

NOT

BE

USED

. M

INIMUM

FORK

LENGTH

IS

42”

TO

PREVENT

DAMAGE

TO

THE

UNIT

;

HOWEVER

, 48”

IS

RECOMMENDED

.

CAUTION

Provisions for forks have been included in the unit base frame.
No other fork locations are approved.

WARNING

T

O PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL

INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED
WHEN INSTALLING THE UNIT.

• Unit must be lifted by the four lifting holes located at

the base frame corners.

• Lifting cables should be attached to the unit with

shackles.

• The distance between the crane hook and the top of

the unit must not be less than 60”.

• Two spreader bars must span over the unit to prevent

damage to the cabinet by the lift cables. Spreader
bars must be of sufficient length so that cables do not
come in contact with the unit during transport.
Remove wood struts mounted beneath unit base
frame before setting unit on roof curb. These struts
are intended to protect unit base frame from fork lift
damage. Removal is accomplished by extracting the
sheet metal retainers and pulling the struts through
the base of the unit. Refer to rigging label on the unit.

Important: If using bottom discharge with roof curb, duct-
work should be attached to the curb prior to installing the
unit. Ductwork dimensions are shown in Roof Curb Installa-
tion Instructions.

Refer to the Roof Curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with the
National Roofing Contractors Association Manual.