APPENDIX A BLOWER PERFORMANCE TABLES

BELT DRIVE

HIGH STATIC DOWN SHOT

CPC/H036 HIGH STATIC BELT DRIVE DOWN SHOT

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

0.6

1692

0.54

1449

0.41

1173

0.29

0.8

1678

0.58

1397

0.44

1107

0.31

854

0.21

1.0

1681

0.65

1381

0.49

1078

0.34

794

0.22

1.2

1681

0.71

1362

0.54

1062

0.39

1.4

1362

0.60

1066

0.44

1.6

1066

0.50

789

0.34

1.8

789

0.40

CPC/H048 HIGH STATIC BELT DRIVE DOWN SHOT

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

0.6

2194

0.85

1886

0.66

1580

0.49

0.8

2113

0.86

1832

0.70

1526

0.52

1219

0.37

1.0

2182

0.98

1776

0.73

1472

0.55

1166

0.39

1.2

2053

1.00

1780

0.80

1440

0.59

1111

0.40

1.4

1759

0.86

1421

0.64

1104

0.46

1.6

1442

0.72

1095

0.50

1.8

1095

0.56

CPC/H060 HIGH STATIC BELT DRIVE DOWN SHOT

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

0.6

2331

1.01

2072

0.80

0.8

2324

1.10

2059

0.87

1791

0.66

1.0

2350

1.21

2058

0.95

1774

0.72

1.2

2367

1.33

2086

1.06

1776

0.79

1.4

2404

1.45

2111

1.17

1805

0.89

1.6

2136

1.28

1835

0.99

1.8

1868

1.10

CPC/H072 HIGH STATIC BELT DRIVE DOWN SHOT

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

0.6

2793

1.64

2603

1.39

2450 1.182 2270

0.97

0.8

2903

1.87

2696

1.57

2369

1.23

2236

1.05

1987

0.82

1.0

2776

1.86

2683

1.69

2445

1.38

2196

1.12

1968

0.90

1.2

2599

1.71

2539

1.57

2310

1.29

1932

0.96

1.4

2424

1.57

2305

1.40

2032

1.11

1.6

2172

1.38

2017

1.19

1.8

1953

1.22

NOTES:

ESP, In

H

2

O

TURNS OPEN

0

1

2

3

4

5

ESP, In

H

2

O

TURNS OPEN

0

1

2

3

4

5

ESP, In

H

2

O

TURNS OPEN

0

1

2

3

4

5

ESP, In

H

2

O

TURNS OPEN

0

1

2

3

4

5

Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P.
SCFM correction for wet coil = 4 %.

Advertising