Curb insulation, cant strips, flashing and general
roofing material are furnished by the contractor.

The curbs must be supported on parallel sides by roof mem-
bers. The roof members must not penetrate supply and re-
turn duct opening areas as damage to the unit might occur.

NOTE: The unit and curb accessories are designed to allow
vertical duct installation before unit placement. Duct
installation after unit placement is not recommended.

A

LL

 

CURBS

 

LOOK

 

SIMILAR

. T

O

 

AVOID

 

INCORRECT

 

CURB

 

POSITIONING

CHECK

 

JOB

 

PLANS

 

CAREFULLY

 

AND

 

VERIFY

 

MARKINGS

 

ON

 

CURB

 

ASSEMBLY

. I

NSTRUCTIONS

 

MAY

 

VARY

 

IN

 

CURB

 

STYLES

 

AND

 

SUPERCEDE

 

INFORMATION

 

SHOWN

.

CAUTION

See the manual shipped with the roof curb for assembly and
installation instructions.

CLEARANCES

36” MIN.

75”

48”

6”

48”

UNIT CLEARANCES

Adequate clearance around the unit should be kept for safety,
service, maintenance, and proper unit operation. A total clear-
ance of 75” on the main control panel side of the unit is rec-
ommended to facilitate possible fan shaft, coil, electric heat
and gas furnace removal. A clearance of 48” is recommended
on all other sides of the unit to facilitate possible compressor
removal, to allow service access and to insure proper venti-
lation and condenser airflow. The unit must not be installed
beneath any obstruction. The unit should be installed re-
mote from all building exhausts to inhibit ingestion of exhaust
air into the unit fresh air intake.

INSULATED
PANELS

ROOF CURB INSTALLATION

ROOF CURB POST-INSTALLATION

CHECKS

After installation, check the top of the curb, duct connection
frame and duct flanges to make sure gasket has been ap-
plied properly. Gasket should be firmly applied to the top of
the curb perimeter, duct flanges and any exposed duct con-
nection frame. If gasket is loose, re-apply using strong
weather resistant adhesive.

P

ROTRUSION

Inspect curb to ensure that none of the utility services (elec-
tric) routed through the curb protrude above the curb.

I

F

 

PROTRUSIONS

 

EXIST

DO

 

NOT

 

ATTEMPT

 

TO

 

SET

 

UNIT

 

ON

 

CURB

I

NFORMATION

 

SHOWN

.

CAUTION

ROOF TOP DUCT CONNECTIONS

Install all duct connections on the unit before placing the unit
on rooftop.

H

ORIZONTAL

D

ISCHARGE

For horizontal discharge, remove the supply and return duct
covers and place them over the vertical discharge return and
supply openings. Install with insulation facing up, using the
longer screws provided in the literature package.

Advertising