GE GEK-45404F User Manual

Page 3

Advertising
background image

GEK-45404

3

DESCRIPTION

These are single-phase, sensitive overvoltage relays of the induction disk construction. They are
equipped with a time dial so as to provide adjustable time delay in their operation. The relays are
principally applicable for sensitive overvoltage ground detection for high-impedance grounded
generators or for ungrounded power systems. The differences among the four relays are as indicated
in Table A below. Each relay is mounted in a standard size S1 drawout case and the outline and
panel drillings are shown in Figs. 14 and 15; Fig. 13 shows the outline for an external capacitor when
used. The internal connections of the relays are indicated in the table. Each relay contains a target
seal-in unit that is used to protect the relay main contacts and control spring from damage due to
breaker-trip current.

TABLE A

CONTINUOUS

RATING**

(VOLTS)

PICKUP

RANGE,

VOLTS

TAPS

CONTACTS

INTERNAL

CONNECTIONS

FIGURE

IAV51D

115

10-40

199

16-64

YES

1NO

1

345

28-112

IAV51K

67

5.4-20

YES

1NO

2

IAV52C

115

9.2

199

16

NO

2NO*

3

345

28

IAV52D

199

16-64

YES

2NO*

4

IAV52K

67

5.4-20

YES

2NO*

5

*

The two normally-open contacts have a common connection; refer to the internal connections of
the relay.

** All relays have a 360 volt 10 second rating.

Advertising