broken delta voltage will therefore be three times the normal delta phase-to-phase voltage with no
fault.

RATINGS

The operating-circuit ratings available are shown in Table I. The operating coil will stand rated
voltage continuously on any tap.

RELAY

VOLTAGE RATINGS

60HZ

50HZ

IAV51D

115

115

199

199

345

345

IAV51K

67

67

IAV52C

115

115

199

199

345

345

IAV52D

199

IAV52K

67

67

The current-closing rating of the contacts is 30 amperes for voltage not exceeding 250 volts. The
current-carrying ratings are affected by the selection of the tap on the seal-in coil, as indicated in
Table II.

TABLE II

FUNCTION

AMPERES

2-Amp Tap

0.2-Amp Tap

Tripping Duty Carry

Continuously

30

3

0

0.3

The 2-ampere tap has a DC resistance of 0.13 ohms and a 60 cycle impedance of 0.53 ohms, while
the 0.2-ampere tap has a 7-ohm DC resistance and a 52-ohm 60 cycle impedance. The tap setting
used on the seal-in element is determined by the current drawn by the trip coil.

The 0.2-ampere tap is for use with trip coils that operate on currents ranging from 0.2 up to 2.0
amperes at the minimum control voltage. If this tap is used with trip coils requiring more than two
amperes, there is a possibility that the 7-ohm resistance will reduce the current to so low a value that
the breaker will not be tripped.

The 2-ampere tap should be used with trip coils that take 2 amperes or more at minimum control
voltage, provided the tripping current does not exceed 30 amperes at the maximum control voltage.
If the tripping current exceeds 30 amperes an auxiliary relay should be used, the connections being