GEK-45404

6

such that the tripping current does not pass through the contacts of the target and seal-in coil of the
protective relay.

BURDENS

Burdens for the various relay types are give in Tables IIIA and B.

TABLE IIIA

60 - Cycle Burdens Rated Voltage

RELAY

TYPES

VOLTAGE

RATING

TAP**SETTING

VOLT-AMPS

POWER

FACTOR

WATTS

1AV51D

115

A(10)

31.4

0.33

10.2

B(15)

27.2

0.57

15.6

C(25)

19.0

0.82

15.6

D(40)

12.3

0.93

11.4

IAV51D

199

A(16)

32.0

0.31

9.9

IAV52D

B(24)

27.9

0.56

15.6

C(40)

20.0

0.81

16.2

D(64)

13.2

0.92

12.2

IAV51D

345

A(28)

41.5

0.37

15.5

B(42)

35.0

0.62

21.6

C(70)

23.9

0.85

20.3

D(112)

13.6

0.95

12.9

IAV51K

67

A(5.4)

34.0

0.31

10.5

IAV52K

B(7.5)

31.0

0.52

15.9

C(12.5)

23.1

0.77

17.7

D(20)

16.0

0.9

14.4

115

No Taps

24.2

0.21

5.0

IAV52C

199

No Taps

32.0

0.31

9.9

345

No Taps

41.5

0.37

15.5

1AV51D

115

A(10)

36.8

0.34

12.6

B(15)

30.8

0.62

19.0

C(25)

20.3

0.86

17.4

D(40)

12.7

0.95

12.0

IAV51D

199

A(16)

25.4

0.28

7.0

B(24)

23.1

0.5

11.5

C(40)

17.8

0.74

13.3

D(64)

12.4

0.88

11.0

TABLE IIIA (CONTINUED)