Greenheck Fan FSD-312 User Manual

Model fsd-312 combination fire smoke dampers, Application, Ratings

Advertising
background image

APPLICATION

Model FSD-312 is a high performance combination fire smoke

damper with class II leakage. High strength airfoil blades ensure the

lowest resistance to airflow in HVAC systems with velocities to 3000

fpm (15.2 m/s) and pressures to 4 in. wg (1 kPa) Model FSD-312 may

be installed vertically (with blades running horizontal) or horizontally

and is rated for airflow and leakage in either direction.

RATINgs

UL 555 Fire Resistance Rating:

Fire Rating:

1½ hours

Dynamic Closure Rating: Actual ratings are size dependent

Max. Velocity:

up to 3000 fpm (15.2 m/s)

Max. Pressure:

4 in. wg (1 kPa)

UL555S Leakage Rating:

Leakage Class:

II

Operational Rating:

Actual ratings are size dependent

Max. Velocity:

up to 3000 fpm (15.2m/s)

Max. Pressure:

4 in. wg (1 kPa)

Maximum Temperature: 350°F (177°C)- depending upon the

actuator

sTANdARd CONsTRuCTION

Frame:

5 in. x 1 in. (127mm x 25 mm)

galvanized steel hat channel with

reinforced corners. A low profile

head and sill are used on sizes less

than 17 in. (432mm)

Blades:

Double skin airfoil shape of

galvanized steel with full length

structural reinforcement. 14 ga.

(2 mm) equivalent thickness.

seals:

Extruded silicone rubber blade seals.

Flexible stainless steel jamb seals.

Linkage:

Concealed in jamb.

Closure device:

RRL 165°F (74°C)

Axles:

1⁄2 in. (13mm) dia. plated steel.

Bearings:

Bronze sleeve type.

sIze LImITATIONs:

minimum size:

8 in. W x 6 in. H

(203 mm W x 152mm H)

maximum size:

Single Section:

32 in. W x 50 in. H

(813mm W x 1270mm H)

Multiple Section:

96 in. W x 50 in. H

(2435mm W x 1270mm H)

Vertical Only:

128 in. W x 100 in. H

(3251mm W x 2540mm H)

OPTIONAL FeATuRes:

• RRL/OCI (Open closed indication switches)

• 165ºF (74°C), 212ºF (100°C), 250ºF (121°C), 350ºF (177°C) RRL’s

available

• TOR (remote override closure allows damper to perform smoke

management functions during a fire emergency.)

• Electric or pneumatic actuators to accomplish smoke

management and system functions.
• POC retaining angles
• Smoke detectors
• Momentary Switch
• Transitions (R, C, O)
• PRV (pneumatic relief valve)
• Security Bars
• Sealed transitions and sleeves

model Fsd-312

Combination Fire smoke dampers

Steel Airfoil Blades

UL 555S Leakage Class II

UL555 1

1

2

Hour Fire Resistance Rating

*W&H dimensions furnished approximately 1/4 in. ( 6 mm) undersize.

(Add sleeve thickness for overall sleeved damper dimension)

Right hand drive is shown. Left hand drive is available upon request.

H*

W*

LH

RH

Model FSD-312 meets the requirements for fire

dampers, smoke dampers and combination fire

smoke dampers established by:

National Fire Protection Association

NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC International Building Codes
ICBO uniform Building Codes
CsFm California state Fire marshal
Fire Damper Listing (#3225-0981:103)
Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)

“uL CLAssIFIed (see complete marking on prod-

uct)”

“uL CLAssIFIed to Canadian safety standards

(see complete marking on product)”

Standard 555 & 555S (Listing #R13317)

R

Greenheck Fan Corporation certifies that the

model FSD-312 shown herein is licensed to

bear the AMCA Seal. The ratings shown are

based on tests and procedures performed

in accordance with AMCA Publication 511

and comply with the requirements of the

AMCA Certified Ratings Programs. The

AMCA Certified Ratings Seal applies to air

performance ratings only.

Installation instructions available at www.greenheck.com