1 before initial start-up, 2 check transfer switch operation, 3 electrical checks – Generac Power Systems 04758-0 User Manual

Page 12: Danger

Advertising
background image

10

The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off

immediately with water;

• Where electrolyte contacts the eyes, immediately

flush thoroughly with water and seek medical
attention; and

• Spilled electrolyte is to be washed down with an

acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) or water. The bicar-
bonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.

Lead-acid batteries present a risk of fire
because they generate hydrogen gas. The
following procedures are to be followed:

• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from your body before

touching the battery by first touching a grounded
metal surface.

Be sure the Auto/Off/Manual switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as
the battery cables are connected.

Be sure the utility power supply is turned off,
or sparking may occur at the battery posts as
you attach the cables and cause an explosion.

2.1

BEFORE INITIAL START-UP

Before starting, complete the following:

1. Set the generator’s main circuit breaker to its

OFF (or open) position.

2. Set the generator's Auto/Off/Manual switch to the

OFF position.

3. Turn OFF the utility power supply to the transfer

switch using the means provided (such as the
utility main line circuit breaker).

4. Check the engine crankcase oil level and, if nec-

essary, fill to the dipstick FULL mark with the
recommended oil. Do not fill above the FULL
mark.

5. Check the fuel supply. Gaseous fuel lines must

have been properly purged and leak tested in
accordance with applicable fuel-gas codes. All
fuel shutoff valves in the fuel supply lines must be
open.

Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.

2.2

CHECK TRANSFER SWITCH
OPERATION

Refer to Section 3.5 (Page 15), of the owner’s manual
for manual operation procedures.

Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned off.
Failure to turn off all power voltage supplies
will result in extremely hazardous and possibly
fatal electrical shock.

2.3

ELECTRICAL CHECKS

Complete electrical checks as follows:

1. Turn on the utility power supply to the transfer

switch using the means provided (such as a utili-
ty main line circuit breaker).

The transfer switch is now electrically “hot.”
Contact with “hot” parts will result in extreme-
ly hazardous and possibly fatal electrical shock.
Proceed with caution.

2. Use an accurate AC voltmeter to check utility

power source voltage across terminals N1 and
N2. Nominal line-to-line voltage should be 240
volts AC.

3. Check utility power source voltage across termi-

nals N1 and the transfer switch neutral lug; then
across terminal N2 and neutral. Nominal line-to-
neutral voltage should be 120 volts AC.

4. When certain that utility supply voltage is com-

patible with transfer switch and load circuit rat-
ings, turn OFF the utility power supply to the
transfer switch.

5. Set the generator's main circuit breaker to its

OFF (or open) position. Initial tests will be con-
ducted at no-load condition.

6. On the generator panel, set the Auto/Off/Manual

switch to MANUAL. The engine should crank and
start.

7. Let the engine warm up for about five minutes to

allow internal temperatures to stabilize. Then, set
the generator’s main circuit breaker to its ON (or
closed) position.

Proceed with caution! Generator power voltage
is now supplied to the transfer switch. Contact
with live transfer switch parts will result in
dangerous and possibly fatal electrical shock.

DANGER

DANGER

DANGER

!

!

Section 2 — Post Installation Start-up and Adjustments

Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators