5 manual transfer operation, Danger – Generac Power Systems 04758-0 User Manual

Page 17

Advertising
background image

15

D.Utility Voltage Pickup Sensor

• This sensor monitors utility power supply volt-

age. When that voltage is restored to above 70
percent of the nominal source voltage, a retrans-
fer time delay starts timing.

E.Retransfer Time Delay

• This timer runs for about 15 seconds.
• At end of a 15-second delay, circuit board action

de-energizes the transfer relay in the transfer
switch.

• Retransfer to utility power source then occurs.

F. Engine Cool-down Timer

• When the load is transferred back to utility power

source, the engine cool-down timer starts timing.

• The timer will run for about one minute, and the

generator will then shut down.

3.5

MANUAL TRANSFER OPERATION

3.5.1 TRANSFER TO GENERATOR

POWER SOURCE

To start the generator and activate the transfer switch
manually, proceed as follows:

1. Set the generator’s main circuit breaker to its

OFF (or open) position.

2. Set the generator’s Auto/Off/Manual switch

to OFF.

3. Turn OFF the utility power supply to the transfer

switch using the means provided (such as a
utility main line circuit breaker).

Do not attempt to activate the transfer switch
manually until all power voltage supplies to
the switch have been positively turned off.
Failure to turn off all power voltage supplies
may result in extremely hazardous and possibly
fatal electrical shock.

4. Use the manual transfer handle inside the trans-

fer switch to move the main contacts to their
“Standby” position, i.e., loads connected to the
standby power source (Figure 3.2).

5. To crank and start the engine, set the

Auto/Off/Manual switch to MANUAL.

6. Let the engine stabilize and warm up for a few

minutes.

7. Set the generator’s main circuit breaker to its ON

(or closed) position. The standby power source
now powers the loads.

Figure 3.2 – Manual Transfer Switch Operation

3.5.2 TRANSFER BACK TO UTILITY POWER

SOURCE

When utility power has been restored, you will want
to transfer back to that source and shut down the
generator. This can be accomplished as follows:

1. Set the generator’s main circuit breaker to its

OFF (or open) position.

2. Let the engine run for a minute or two at no-load

to stabilize the internal temperatures.

3. Set the generator’s Auto/Off/Manual switch to

its OFF (or open) position. The engine should
shut down.

4. Check that utility power supply to the transfer

switch is turned OFF.

Do not attempt to activate the transfer switch
manually until all power voltage supplies
to the switch have been positively turned off.
Failure to turn off all power voltage supplies
may result in extremely hazardous and possibly
fatal electrical shock.

5. Use the manual transfer handle inside the trans-

fer switch to move the main contacts back to their
“Utility” position, i.e., loads connected to the util-
ity power source (Figure 3.2).

6. Turn ON the utility power supply to the transfer

switch using the means provided.

7. Set the system to automatic operation as outlined

in “Automatic Transfer Operation,” Section 3.3
(Page 14).