Application data ofsd-212, Actuator space envelopes, Wall opening sizing – Greenheck Fan Steel 3V Blades OFSD-212 User Manual

Page 6: Sleeve information, Specifications

Advertising
background image

X

Y

Grille
(Supplied by
others)

Factory supplied thermal
blanket around sleeve

Fire rated barrier

Combination Fire
Smoke Damper

7 1⁄2

"

Max.

5 in.

A

Sleeve Length

Actuator Space Envelopes

The drawing below and corresponding table show the minimum dimensions

required for internal actuator mounting on OFSD-212s. The standard mounting

locations provide enough space for the mounting of actuators and controls plus

allowing space for a grille and duct connection (see Sleeve Length below).

Wall Opening Sizing

To accommodate for sleeve and thermal blanket thickness,

the wall opening must be oversized by

3

8

in. (9.5mm) as

shown. For example, if the nominal damper size required

is 18 in. x 14 in. (457mm x 356mm), the wall opening size

needs to be 18

3

8

in. x 14

3

8

in. (467mm x 365mm). The

damper itself is undersized

1

4

in. (6mm) on each dimension

for an actual damper size of 17

3

4

in. x 13

3

4

in. (451mm x

349mm). This is also the inside dimensions of the sleeve (for

grille considerations).

Application data

OFSd-212

Sleeve Information

‘Sleeve Length’ = depth of Grille (or Register)

+ X (Actuator: see table above)

+ 5 in. [127mm] (Damper Width)

+ 1.25 in. [31.8mm] (for duct connection)

(round up to nearest length: 14 in., 16 in., 18 in.,

or 20 in. [356, 406, 457, 508mm])

‘Sleeve Gauge’ = 16 Ga. or 20 Ga. (1.5mm or 1mm)

Nominal Damper

Width +

3

8

in.

Nominal

Damper

Height +

3

/

8

in.

Wall

Fire Smoke Damper

With Sleeve And

Thermal Blanket

/

Combination Fire Smoke Dampers meeting the following

specifications shall be furnished and installed where shown on

plans and/or as described in schedules. Dampers shall meet the

requirements of NFPA 80, 90A, 92A, 92B, 101 & 105 and further shall

be tested, rated and labeled in accordance with the latest edition

of UL Standards 555 and 555S. Dampers shall have a UL555 fire

rating of 1½ hours and be of low leakage design qualified to UL 555S

Leakage Class II.

Each damper /actuator combination shall have a UL555S elevated

temperature rating of 250°F (121°C) minimum and shall be operational

and dynamic rated to operate at maximum design air flow at its

installed location. Each damper shall be supplied with an appropriate

actuator installed by the damper manufacturer at the time of damper

fabrication. Damper actuator shall be (specifier select one of the

following) electric type for 120 (24 or 230) Volt operation.

Damper blades shall be 16 ga. (1.5mm) galvanized steel 3V type with

three longitudinal grooves for reinforcement. Damper frame shall

be galvanized steel formed into a structural hat channel shape with

reinforced corners. Bearings shall be sintered bronze sleeve type

rotating in extruded holes in the damper frame. Blade edge seals

shall be silicone rubber designed to inflate and provide a tighter seal

against leakage as pressure on either side of the damper increases.

Jamb seals shall be stainless steel compression type. Blades shall be

completely symmetrical relative to their axle pivot point, presenting

identical resistance to airflow in either direction or pressure on either

side of the damper. Each damper shall be supplied with a factory

mounted sleeve; sleeve shall be wrapped with UL approved thermal

barrier material.

The Damper Manufacturer's submittal data shall certify all air

performance pressure drop data is licensed in accordance with the

AMCA Certified Ratings Program for Test Figures 5.2, 5.3, and 5.5.

Damper air performance data shall be developed in accordance with

the latest edition of AMCA Standard 500-D. Dampers shall be labeled

with the AMCA Air Performance Seal.

Damper must be rated for mounting vertically (with blades running

horizontal) or horizontally and be UL 555S rated for leakage and

airflow in either direction through the damper. Each damper shall be

supplied with a 165°F (74°C) RRL.

The basis of design is Greenheck Model OFSD-212.

Specifications

Copyright ©2006 Greenheck Fan Corporation

OFSD-212 Rev 3 June 2006

Actuator Space

Envelopes

Honeywell

ML-4XXX series

MS4XXX series

MS4120 series

'X' dimension

5.88 in. (149mm)

5.88 in. (149mm)

Minimum Width

12 in. (305mm)

12 in. (305mm)

Minimum Height

12 in. (305mm)

12 in. (305mm)

Advertising