Grease Grabber Triple Play Kitchen Exhaust Pollution Control System

Table of Contents

Grease Grabber Triple Play

System Function

Grease Grabber Triple Play is a 3-stage mechanical air
filtration unit, with an additional carbon filter module,
designed for two specific functions:
• Remove smoke/grease particulate from kitchen

exhaust.

• Remove odor molecules from kitchen exhaust.

System Components

Cabinet Assembly
The unit body is shipped on a common mounting rail
ready for installation. If the unit was ordered with an
exhaust fan, the fan will also be mounted as part of
the cabinet assembly.

Filters
Filter quantity for each filter stage is based on unit
size. A consistent quantity of filters is provided for
each stage of filtration (pre-filter, bag filter, and rigid
final filter). Quantity of carbon panels will vary based
upon unit exhaust rate.

Remote Status Indicator (See Page 6)
At time of delivery, a remote status indicator is
mounted within the rigid filter section of the unit body.
This item must be removed and mounted remotely in
the cooking area prior to unit start-up.

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Rigging/Placing Equipment . . . . . . . . . . . . . . . . . . 4

Duct Connections . . . . . . . . . . . . . . . . . . . . . . . . . 4

Electrical Connections . . . . . . . . . . . . . . . . . . . . . . 4

Fire System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Filter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Filter Status Indicator . . . . . . . . . . . . . . . . . . . . . . 5

Filter Replacement . . . . . . . . . . . . . . . . . . . . . . . . . 6

Carbon Panel Replacement . . . . . . . . . . . . . . . . . 6
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Regular Scheduled Maintenance . . . . . . . . . . . . . 6

Replacement Filter/Parts Ordering . . . . . . . . . . . . 6
Figures #1 and #2 . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
Maintenance Log . . . . . . . . . . . . . . . . . . . . . . . . 10-11

Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

NOTE

Grease Grabber Triple Play must be connected to a
listed exhaust hood assembly and must be installed
in accordance with local building codes, NFPA 96
and NEC.

NOTE

Grease Grabber Triple Play is not intended for use
with solid fuel cooking appliances.

NOTE

The unit must be installed with a minimum 18 inch
clearance to combustible materials and must be
installed as part of a listed duct assembly.

Filter stages 1, 2 and 3 are mechanical air filters of
progressive filtration efficiency that retain the smoke
and grease particles.
Each filter stage is monitored by an individual
pressure switch that signals when a particular filter
stage needs replacing. The pressure switches are
located inside the Pressure Switch Enclosure located
on the access door side of Triple Play housing,
between filter stages 2 and 3. When a filter stage
requires replacement, a signal from the pressure
switch lights an LED located on the remote mounted
Filter Status Indicator. This enclosure must be field
mounted in an area convenient for monitoring by the
cook staff.

Unit Size

Filter Quantity (each)

10-10

1

10-20

2

10-30

3

20-20

4

20-30

6

20-40

8

30-30

9

30-40

12

40-40

16

40-50

20